Siemens Sinamics G120 Series Parameter Manual page 236

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
r2197.0...12
CO/BO: Monitoring word 1 / Monitor Wd1
PM250
Access level: 2
PM260
Unit: -
Description:
Monitoring word 1 which indicates the state of monitor functions.
Each bit represents one monitor function.
Bit field:
Bit
Signal name
00
f_act <= P1080 (f_min)
01
f_act <= P2155 (f_1)
02
f_act > P2155 (f_1)
03
f_act > zero
04
f_act >= setp. (f_set)
05
f_act <= P2167 (f_off)
06
f_act >= P1082 (f_max)
07
f_act == setp. (f_set)
08
Act. current r0068 <= P2170
11
Load missing
12
f_act > P1082 with delay
r2198.0...12
CO/BO: Monitoring word 2 / Monitor Wd2
Access level: 2
Unit: -
Description:
Monitoring word 2 which indicates the state of monitor functions.
Each bit represents one monitor function.
Bit field:
Bit
Signal name
00
|f_act| <= P2157 (f_2)
01
|f_act| > P2157 (f_2)
02
|f_act| <= P2159 (f_3)
03
|f_act| > P2159 (f_3)
04
|f_set| < P2161 (f_min_set)
05
f_set > 0
06
Motor blocked
07
Motor pulled out
08
| I_act r0068 | < P2170
09
| m_act | > P2174 & setpoint reached
10
| m_act | > P2174
11
Belt failure warning
12
Belt failure trip
1-236
P-Group: Messages
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
P-Group: Messages
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned16
Data set: -
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: Unsigned16
Data set: -
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240s dpCu240s dp-fCu240sCu240s pn

Table of Contents