p9810
PROFIsafe destination address / F dest address
CU240S DP-F
Access level: 2
Quick comm. NO
Can be changed: T
Min
0
Description:
Defines the PROFIsafe destination address for the communication.
The PROFIsafe destination address is identical to the PROFIBUS address by default.
This parameter can be changed via a user-entered value.
Note:
Valid PROFIsafe address settings:
1 ... 65534
0: default, forces PROFIsafe address to be identical with the PROFIBUS address.
If the PROFIsafe destination address is set manually to a value which is unequal to the PROFIBUS address, it will
not be automatically adjusted when the PROFIBUS address is changed.
This applies when the PROFIBUS address is set via DIP switches as well as via parameter p0918.
p9850
SI Safe Digital Input debounce delay time / SI Debounce FDI
CU240S DP-F
Access level: 3
Quick comm. NO
Can be changed: -
Min
0.000 [s]
Description:
Double of parameter p9650. See there.
Note:
The debounce delay time in p9850 is entered in seconds!
p9851
SI Safe Digital Input filter delay time / SI Filt. time FDI
CU240S DP-F
Access level: 3
Quick comm. NO
Can be changed: -
Min
0.000 [s]
Description:
Double of parameter p9651. See there.
Note:
The filter delay time in p9851 is entered in seconds!
p9880
SI braking ramp delay / SI braking delay
CU240S DP-F
Access level: 3
Quick comm. NO
Can be changed: -
Min
0.010 [s]
Description:
Double of parameter p9680. See there.
Note:
The delay time in p9880 is entered in seconds!
p9881
SI braking ramp down time / SI ramp down time
CU240S DP-F
Access level: 3
Quick comm. NO
Can be changed: -
Min
0.100 [s]
Description:
Double of parameter p9681. See there.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Communications
Active: NO
Max
65534
P-Group: Safety Integrated
Active: NO
Max
2.000 [s]
P-Group: Safety Integrated
Active: NO
Max
0.100 [s]
P-Group: Safety Integrated
Active: NO
Max
99.000 [s]
P-Group: Safety Integrated
Active: NO
Max
99.000 [s]
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Floating Point
Data set: -
Factory setting
0.050 [s]
Data type: Floating Point
Data set: -
Factory setting
0.005 [s]
Data type: Floating Point
Data set: -
Factory setting
0.250 [s]
Data type: Floating Point
Data set: -
Factory setting
10.000 [s]
1-295