Siemens Sinamics G120 Series Parameter Manual page 257

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Example:
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2
FFBs will be calculated in following order:
P2802[3], P2801[3] , P2801[4], P2802[4]
Index:
[0] = Enable timer 1
[1] = Enable timer 2
[2] = Enable timer 3
[3] = Enable timer 4
[4] = Enable ADD 1
[5] = Enable ADD 2
[6] = Enable SUB 1
[7] = Enable SUB 2
[8] = Enable MUL 1
[9] = Enable MUL 2
[10] = Enable DIV 1
[11] = Enable DIV 2
[12] = Enable CMP 1
[13] = Enable CMP 2
Dependency:
Set P2800 to 1 to enable function blocks.
All active function blocks will be calculated in every 132 ms.
p2803[0...2]
Enable FastFFBs / Enable FastFFBs
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
0
Description:
Fast free function blocks (FFB) are enabled in two steps.
1. Parameter P2803 enables all fast free function blocks , normally (P2803 = 1).
2. Parameters P2801 and P2802 respectively, enable each fast free function block individually (7 > P2801[x] > 3
or 7 > P2802[x] > 3).
Values:
0:
1:
Dependency:
All active function blocks will be calculated in every 8 ms.
Note:
Attention: p2200 and p2803 are locked parameter against each other. PID and FFB of the same dataset cannot be
active at same time.
p2810[0...1]
BI: AND 1 / AND 1
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
-
Description:
P2810[0], P2810[1] define inputs of AND 1 element, output is P2811.
p2810
Index:
[0] = Binector input 0 (BI 0)
[1] = Binector input 1 (BI 1)
Dependency:
P2801[0] is active level for the AND element.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Disable
Enable
p2800 p2801[0]
A
&
C
Index0
B
Index1
P-Group: Technology
Active: NO
Max
1
P-Group: Technology
Active: NO
Max
-
A
B
0
0
0
1
r2811
1
0
1
1
Parameters
List of Parameters
Data type: Unsigned16
Data set: CDS
Factory setting
0
Data type: Unsigned32
Data set: -
Factory setting
0
C
0
0
0
1
1-257