Siemens Sinamics G120 Series Parameter Manual page 394

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Faults and Alarms
List of Fault and Alarm messages
A00590
Encoder feedback loss warning
Reaction:
NONE
Acknowledge:
NONE
Cause:
Signal from Encoder lost; Inverter might have switched to sensorless vector control.
Check also alarm value r0947:
r0949 = 0: Encoder signal lost.
r0949 = 5: Encoder not configured in P0400, but required for sensored control (P1300 = 21 or 23).
Remedy:
Stop inverter and then
Check encoder fitted. If encoder fitted and r0949 = 5, select encoder type via P0400.
If encoder fitted and r0949 = 6, check connections between encoder module and inverter.
If encoder not fitted and r0949 = 5, select SLVC mode (P1300 = 20 or 22).
If encoder not fitted and r0949 = 6, set P0400 = 0.
If encoder fitted, check correct encoder selected (check encoder setup in P0400).
Check connections between encoder and inverter.
Check that encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in r0061).
Increase encoder loss threshold in P0492.
A00600
RTOS Overrun Warning
Reaction:
NONE
Acknowledge:
NONE
Cause:
Internal time slice overrun
Remedy:
Contact Service Department
A00700
PROFIBUS: Parameter or configuration error
Reaction:
NONE
Acknowledge:
NONE
Cause:
wrong parameter and/or configuration telegram
Remedy:
check parameter and/or configuration telegram
A00701
PROFIBUS: DoubleWord error
Reaction:
NONE
Acknowledge:
NONE
Cause:
error in double word reference table
Remedy:
power cycle
A00702
PROFIBUS: no bus detection
Reaction:
NONE
Acknowledge:
NONE
Cause:
connection error, no bus initialization (no master), no clear bus signal, ...
Remedy:
check the cables and the bus hardware
A00703
PROFIBUS: no reference values
Reaction:
NONE
Acknowledge:
NONE
Cause:
no or empty control word 1 received
Remedy:
check bus transmission
A00704
PROFIBUS: loose of links
Reaction:
NONE
Acknowledge:
NONE
Cause:
lost subscriber information
Remedy:
temporary, if permanent the fault detection is activated
3-394
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240s dpCu240s dp-fCu240sCu240s pn

Table of Contents