Siemens Sinamics G120 Series Parameter Manual page 94

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
r0807.0
BO: Displays client access / Displays client ac
Access level: 3
Unit: -
Description:
Binector output to display whether command and setpoint source is connected to an external client.
Bit field:
Bit
Signal name
00
Master control active
p0809[0...2]
Copy Command Dataset (CDS) / Copy CDS
Access level: 2
Quick comm. NO
Can be changed: T
Min
0
Description:
Calls 'Copy Command Dataset (CDS)' function.
The list of all Command Datasets (CDS) parameters is shown in Section 1.3 of this Parameter List (PLI).
Example:
Copying of all values from CDS0 to CDS2 can be accomplished by the following procedure:
P0809[0] = 0 Copy from CDS0
P0809[1] = 2 Copy to CDS2
P0809[2] = 1 Start copy
Index:
[0] = Copy from CDS
[1] = Copy to CDS
[2] = Start copy
Note:
Start value in index 2 is automatically reset to '0' after execution of function.
p0810
BI: CDS bit 0 (Hand/Auto) / CDS bit 0
Access level: 2
Quick comm. NO
Can be changed: U, T
Min
-
Description:
Selects command source from which to read Bit 0 for selecting a Command Dataset (CDS).
The actual selected Command Dataset (CDS) is displayed in parameter r0054.15 (CDS bit 0) and r0055.15 (CDS
bit 1).
The actual active Command Dataset (CDS) is displayed in parameter r0050.
Example:
Typical procedure for CDS switch-over:
CDS0: Command source via terminal and setpoint source via analog input (AI)
CDS1: Command source via USS on RS232 and setpoint source via MOP
CDS switch-over takes place via digital input 3 (DI3)
Steps:
1. Commissioning of inverter / drive
2. CDS0 set parameters (P0700[0] = 2 and P1000[0] = 2)
3. Connect P0810 (P0811 if necessary) with the source of CDS switch-over (P0704[0] = 99, P0810 = 722.3)
4. Copy CDS0 to CDS1 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2)
5. Change CDS1 parameter as required (set parameters for CDS2 [P0700 = 4 and P1000 = 1])
Note:
P0811 is also relevant for Command Dataset (CDS) set selection.
1-94
P-Group: Commands
1 signal
Yes
P-Group: Commands
Active: NO
Max
2
P-Group: Commands
Active: NO
Max
-
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned16
Data set: -
0 signal
FP
No
-
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Unsigned32
Data set: -
Factory setting
0