Siemens Sinamics G120 Series Parameter Manual page 248

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
p2267
Max. value for PID feedback / PID fdbck max. val
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
-200.00 [%]
Description:
Sets the upper limit for the value of the feedback signal in [%].
Notice:
When PID is enabled (P2200 = 1) and the signal rises above this value, the inverter will trip with F0222 .
Note:
p2267 = 100 % corresponds to 4000 hex.
p2268
Min. value for PID feedback / PID fdbck min. val
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
-200.00 [%]
Description:
Sets lower limit for value of feedback signal in [%].
Notice:
When PID is enabled (P2200 = 1) and the signal drops below this value, the inverter will trip with F0221.
Note:
P2268 = 100 % corresponds to 4000 hex.
p2269
Gain applied to PID feedback / PID feedback gain
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
0.00
Description:
Allows the user to scale the PID feedback as a percentage value [%].
A gain of 100.0 % means that feedback signal has not changed from its default value.
p2270
PID feedback function selector / PID fdbck fnct sel
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
0
Description:
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269 (gain
applied to PID feedback).
Values:
0:
1:
2:
3:
1-248
Disabled
Square root (root(x))
Square
(x*x)
Cube
(x*x*x)
P-Group: Technology
Active: YES
Max
200.00 [%]
P-Group: Technology
Active: YES
Max
200.00 [%]
P-Group: Technology
Active: YES
Max
500.00
P-Group: Technology
Active: YES
Max
3
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Floating Point
Data set: -
Factory setting
100.00 [%]
Data type: Floating Point
Data set: -
Factory setting
0.00 [%]
Data type: Floating Point
Data set: -
Factory setting
100.00
Data type: Unsigned16
Data set: -
Factory setting
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240s dpCu240s dp-fCu240sCu240s pn