Siemens Sinamics G120 Series Parameter Manual page 211

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

p2042
Selection of ident number / Ident nb
Access level: 3
Quick comm. NO
Can be changed: T
Min
0
Description:
Selects if native ident number (0) or NAMUR ident number (1) is send to the PLC.
Values:
0:
1:
Note:
After changing P2042, a power cycle must be done to have changes take effect.
See also : Switching to / from Namur in the description of parameter P0922.
r2050[0...7]
CO: PZD from Fieldbus / PZD from FB
CU240S DP
Access level: 3
CU240S DP-F
Unit: -
CU240S PN
Description:
Displays PZD received from Fieldbus.
PZD
STW
HSW
...
Index:
[0] = Received word 0
[1] = Received word 1
[2] = Received word 2
[3] = Received word 3
[4] = Received word 4
[5] = Received word 5
[6] = Received word 6
[7] = Received word 7
Note:
The control words can be viewed as bit parameters r2090 and r2091.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Native
Namur
Process data
Control word
Main setpoint
PZD4
PZD3
PZD2
depends on setting in P0922
Fieldbus
P-Group: -
Active: NO
Max
1
P-Group: Communications
r2050
[0]
[1]
[2]
[3]
[7]
PZD1
STW1
PZD mapping to parameter r2050
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Unsigned16
Data set: -
r2090
1-211