Parameters
List of Parameters
p2016[0...7]
CI: PZD to USS on RS232 / PZD->USS
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Selects signals to be transmitted to serial interface via USS on RS232.
STX
LGE
ADR
PKW
PZD
BCC
ZSW
HIW
PZD mapping from parameter P2016
This parameter allows the user to define the source of the status words and actual values for the reply PZD.
Index 0 cannot be changed and contains always statusword 1.
Example:
P2016[0] = 52.0 (default). In this case, the value of r0052 (CO/BO: Status word) is transmitted as 1st PZD to the
USS on RS232.
Index:
[0] = Transmitted word 0
[1] = Transmitted word 1
[2] = Transmitted word 2
[3] = Transmitted word 3
[4] = Transmitted word 4
[5] = Transmitted word 5
[6] = Transmitted word 6
[7] = Transmitted word 7
If r0052 not indexed, display does not show an index (".0" ).
Note:
1-204
r0052
P2016
r0052
[0]
[1]
r0021
[2]
[3]
r0053
.
r0053
.
.
[7]
Start of text
Length
Address
Parameter ID value
Process data
Block check character
Status word
Main actual value
P-Group: Communications
Active: NO
Max
-
PZD4
PZD3
ZSW2
PZD
BCC
Process data
Parameter
USS telegram
USS on RS232
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned32
Data set: -
Factory setting
52[0]
PZD2
PZD1
HIW
ZSW1
P2012
PKW
ADR
LGE
STX