r0067
CO: Act. output current limit / Outp cur limit
PM240
Access level: 3
Unit: [A]
Description:
Displays valid maximum output current of inverter.
Parameter r0067 is influenced/determined by the following factors:
•
Rated motor current P0305
•
Motor overload factor P0640
•
Motor protection in dependency of P0610
•
r0067 is less than or equal to maximum inverter current r0209
•
Inverter protection in dependency of P0290
Note:
A reduction of r0067 may indicate an inverter overload or a motor overload.
r0067
CO: Act. output current limit / Outp cur limit
PM250
Access level: 3
PM260
Unit: [A]
Description:
Displays valid maximum output current of inverter.
Parameter r0067 is influenced/determined by the following factors:
•
Rated motor current P0305
•
Motor overload factor P0640
•
Motor protection in dependency of P0610
•
r0067 is less than or equal to maximum inverter current r0209
•
Inverter protection in dependency of P0290
•
r0067 is affected by the regeneration power limit when regenerating
Note:
A reduction of r0067 may indicate an inverter overload or a motor overload.
r0068
CO: Output current / Output current
Access level: 3
Unit: [A]
Displays unfiltered [rms] value of motor current [A]. This value is available filtered (r0027) and unfiltered (r0068).
Description:
Note:
Used for process control purposes (in contrast to r0027, which is filtered and used as display value).
r0069[0...5]
CO: Act. phase currents / Act. phase cur
Access level: 4
Unit: [A]
Description:
Displays measured phase currents.
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
[3] = Offset U_phase
[4] = Offset V_phase
[5] = Offset W_phase
r0070
CO: Act. DC-link voltage / Act. Vdc
Access level: 3
Unit: [V]
Description:
Displays DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Note:
Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered and used as dis-
play value).
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Converter
Parameters
List of Parameters
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
1-29