p1717[0...2]
Integral time current controller / Int.time cur. ctrl
Access level: 4
Quick comm. NO
Can be changed: U, T
Min
1.0 [ms]
Description:
Enters integral time of current controller.
r1718
CO: Output of Isq controller / Outp. Isq ctrl
Access level: 4
Unit: [V]
Description:
Displays actual output of Isq current (torque current) controller (PI controller).
It contains the proportional and integral part of the PI controller.
r1719
CO: Integral output of Isq ctrl. / Int. outp. Isq
Access level: 4
Unit: [V]
Description:
Displays integral output of Isq current (torque current) controller (PI controller).
r1723
CO: Output of Isd controller / Outp. Isd ctrl
Access level: 4
Unit: [V]
Description:
Displays actual output of Isd current (flux current) controller (PI controller).
It contains the proportional and integral part of the PI controller.
r1724
CO: Integral output of Isd ctrl. / Int. outp. Isd
Access level: 4
Unit: [V]
Description:
Displays integral output of Isd current (flux current) controller (PI controller).
r1725
CO: Integral limit of Isd ctrl. / Int. limit Isd
Access level: 4
Unit: [V]
Description:
Displays limit of integral output voltage setpoint of Isd current controller.
r1728
CO: Decoupling voltage / Decoupl. volt
Access level: 4
Unit: [V]
Description:
Displays actual output voltage setpoint of cross channel decoupling.
p1740
Gain for oscillation damping / Oscill. damp. gain
Access level: 3
Quick comm. NO
Can be changed: U, T
Min
0.000
Description:
Sets oscillation damping gain for sensorless vector control at low frequencies. The oscillation damping subtracts
the result of a delayed differential (DT1) from the setpoint frequency.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Closed-loop control
Active: YES
Max
50.0 [ms]
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
P-Group: Closed-loop control
Active: YES
Max
10.000
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Factory setting
4.1 [ms]
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Factory setting
0.000
1-179