Start/Stop Mode - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
DI1
DI2
DI3
DI4
DI5
DI6
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
20.27
Jogging 2 start
source
21

21 Start/stop mode

21.01
Start mode
Fast
Description
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
If enabled by parameter
source for the activation of jogging function 2. (Jogging
function 2 can also be activated through fieldbus regardless
of parameter 20.25.)
1 = Jogging 2 active.
For the selections, see parameter
source.
Notes:
• If both jogging 1 and 2 are activated, the one that was
activated first has priority.
• This parameter cannot be changed while the drive is
running.
Start and stop modes; emergency stop mode and signal
source selection; DC magnetization settings.
Selects the motor start function for the vector motor control
mode, ie. when
99.04 Motor control mode
Notes:
• The start function for the scalar motor control mode is
selected by parameter
• Starting into a rotating motor is not possible when DC
magnetizing is selected
• This parameter cannot be changed while the drive is
running.
See also section
DC magnetization
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is determined automatically, being typically
200 ms to 2 s depending on motor size. This mode should be
selected if a high break-away torque is required.
status, bit 0)
status, bit 1)
status, bit 2)
status, bit 3)
status, bit 4)
status, bit 5)
(see page 273)
(see page 273)
(see page 273)
(see page 266)
(see page 266)
(see page 266)
on page 162) -
20.25 Jogging
enable, selects the
20.26 Jogging 1 start
is set to Vector.
21.19 Scalar start
mode.
(Fast
or
Const
time).
(page 70).
Parameters 209
Def/FbEq16
2
3
4
5
6
7
18
19
20
24
25
26
Not selected
Automatic
0