Start/Stop - ABB ACS850 Firmware Manual

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

No.
Name/Value
09.20
Option slot1
09.21
Option slot2
09.22
Option slot3
10

10 Start/stop

10.01
Ext1 start func
Not sel
In1
3-wire
FBA
D2D
In1F In2R
In1St In2Dir
Description
Displays the type of the optional module in option slot 1.
0 = No option, 1 = No comm, 2 = Unknown, 3 = FEN-01,
4 = FEN-11, 5 = FEN-21, 6 = FIO-01, 7 = FIO-11,
8 = FPBA-01, 9 = FPBA-02, 10 = FCAN-01, 11 = FDNA-01,
12 = FENA-01, 13 = FENA-02, 14 = FLON-01,
15 = FRSA-00, 16 = FMBA-01, 17 = FFOA-01,
18 = FFOA-02, 19 = FSEN-01, 20 = FEN-31, 21 = FIO-21,
22 = FSCA-01, 23 = FSEA-21
Displays the type of the optional module in option slot 2. See
signal
09.20 Option
slot1.
Displays the type of the optional module in option slot 3. See
signal
09.20 Option
slot1.
Start/stop/direction etc. signal source selections.
Selects the source of start and stop commands for external
control location 1 (EXT1).
Note: This parameter cannot be changed while the drive is
running.
No start or stop command sources selected.
The source of the start and stop commands is selected by
parameter
10.02 Ext1 start
source bit are interpreted as follows:
State of source
Command
(via par 10.02)
0 - > 1
Start
1 - > 0
Stop
The sources of the start and stop commands is selected by
parameters
10.02 Ext1 start in1
state transitions of the source bits are interpreted as follows:
State of source 1
State of source 2
(via par. 10.02)
(via par. 10.03)
0 - > 1
1
1 - > 0
Any
Any
0
The start and stop commands are taken from the fieldbus.
The start and stop commands are taken from another drive
through the D2D (Drive-to-drive) Control Word.
The source selected by
start signal, the source selected by
reverse start signal.
State of source 1
State of source 2
(via par. 10.02)
(via par. 10.03)
0
0
1
0
0
1
1
1
The source selected by
(0 = stop, 1 = start), the source selected by
in2
is the direction signal (0 = forward, 1 = reverse).
in1. The state transitions of the
and
10.03 Ext1 start
Command
Start
Stop
Stop
10.02 Ext1 start in1
is the forward
10.03 Ext1 start in2
Command
Stop
Start forward
Start reverse
Stop
10.02 Ext1 start in1
is the start signal
10.03 Ext1 start
Parameters 79
FbEq
1 = 1
1 = 1
1 = 1
0
1
2
in2. The
3
4
5
is the
6

Advertisement

Table of Contents
loading

Table of Contents