Alternative ACS 400V Operation Modes (Hardwire Connections)

Start / Stop and External Control Signal 0-10 V

Set DIP switches to voltage signal positions
Start signal is given by activating DI1 (11)
Control signal 0-10 VDC from external regulator is connected to AI1 (2, 3)
Two constant speeds are possible, if 8, 14 and 8, 15 are connected using a switch between 14 and
15, see page 14
External control signal 0-10V
Start/Stop
12
DIP switches
AI1: 0- 10 V
AI2: 0- 10 V
X1
SCR
Screen control signal cable
1
AI1
+ Control signal 0 - 10V
2
AGND
-
3
+10V
+ Reference voltage 10 VDC
4
AI2
+ Pressure sensor 0 - 10V
5
AGND
-
6
Output frq 0 - 50Hz <=> 0 - 20mA
AO1
7
AGND
8
+24V
+ Auxiliary voltage 24 VDC
9
DCOM1
10
DI1
Start / Stop
11
DI2
Activate PID control
12
DI3
13
Select setpoint1 / setpoint2
DI4
14
Constant speed 1
DI5
Constant speed 2
15
DCOM2
16
RO1C
17
Fault = 17-19
RO1A
breaks
18
RO1B
19
RO2C
20
RO2A
21
RO2B
22
Running =
20 connected to 22