Programmable Analog Inputs - ABB ACS850 Firmware Manual

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

when the pressure falls under the predefined minimum level and the wake-up delay
has passed.
Motor Speed
Sleep level
(27.23)
Actual value
Non-inverted (source of
Wake-up level
(27.23)
Actual value
Wake-up level
(27.23)
Inverted (source of
Settings
Parameter group
27 Process PID
The PID control macro can be activated from the control panel main menu by
selecting ASSISTANTS – Firmware assistants – Application Macro – PID control. See
also page 56.

Programmable analog inputs

The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2...10 V or -10...10 V) or current (0/4...20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
t
= Sleep delay (27.24)
d
t
= Wake-up delay (27.26)
wd
t<t
t
d
d
STOP
27.23
= 0)
27.23
= 1)
(page 139).
Program features 41
SLEEP MODE
START
t
wd
t
wd
Time
Time
Time