ABB ACS850 Firmware Manual page 94

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

94 Parameters
No.
Name/Value
13.24
AI5 max scale
-32768.000 ...
32768.000
13.25
AI5 min scale
-32768.000 ...
32768.000
13.26
AI6 filt time
0.000 ... 30.000 s
13.27
AI6 max
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
13.28
AI6 min
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
Description
Defines the real value that corresponds to the maximum
analogue input AI5 value defined by parameter
max.
13.24
13.23
Real value corresponding to maximum AI5 value.
Defines the real value that corresponds to the minimum
analogue input AI5 value defined by parameter
min. See the drawing at parameter
Real value corresponding to minimum AI5 value.
Defines the filter time constant for analogue input AI6. See
parameter
13.01 AI1 filt
Filter time constant.
Defines the maximum value for analogue input AI6. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
AI6 maximum value.
Defines the minimum value for analogue input AI6. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
AI6 minimum value.
13.22 AI5
AI (scaled)
AI (mA/V)
13.22
13.25
13.23 AI5
13.24 AI5 max
time.
FbEq
1000 = 1
scale.
1000 = 1
1000 = 1 s
1000 = 1 unit
1000 = 1 unit