178 Parameters
No.
Name/Value
44.24
Val count2 func
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
44.25
Val count2 src
Speed rpm
Pointer
44.26
Val count2 lim
0 ... 2147483647
44.27
Val count2 div
1 ... 2147483647
44.28
Val cnt2 alm sel
Value2
Mot bearing
44.29
Fan ontime lim
0...35791394.1
44.30
Runtime lim
0...35791394.1
44.31
Runtime alm sel
Device clean
Add cool fan
Cabinet fan
Dc-capacitor
Description
Configures value counter 2. This counter measures, by
integration, the area below the signal selected by parameter
44.25 Val count2
src. When the total area exceeds the limit
set by parameter
44.26 Val count2
enabled by bit 1 of this parameter).
The signal is sampled at 1-second intervals. Note that the
scaled (see the "FbEq" column at the signal in question) value
of the signal is used.
The current value of the counter is readable from parameter
04.14 Counter
value2. Bit 5 of
that the counter has exceeded the limit.
Selects the signal to be monitored by value counter 2. See
parameter
44.24 Val count2
01.01 Motor speed rpm
Value pointer setting (see
63).
Sets the alarm limit for value counter 2. See parameter
Val count2
func.
Alarm limit for value counter 2.
Divisor for value counter 2. The value of the monitored signal
is divided by this value before integration.
Divisor for value counter 2.
Selects the alarm for value counter 2. See parameter
Val count2
func.
Pre-selectable alarm for value counter 2.
Pre-selectable alarm for value counter 2.
Sets the limit for the cooling fan on-time counter. The counter
monitors signal
01.28 Fan on-time
signal reaches the limit, alarm
is given.
Alarm limit for cooling fan on-time.
Sets the limit for the drive run-time counter. The counter
monitors signal
01.27 Run-time counter
the signal reaches the limit, the alarm specified by parameter
44.31 Runtime alm sel
is given.
Alarm limit for the drive run-time counter.
Selects the alarm for the drive run time counter.
Pre-selectable alarm for the drive run time counter.
Pre-selectable alarm for the drive run time counter.
Pre-selectable alarm for the drive run time counter.
Pre-selectable alarm for the drive run time counter.
lim, an alarm is given (if
06.15 Counter status
func.
(see page 64).
Terms and abbreviations
(see page 64). When the
2056 COOLING FAN (0x5081)
(see page 64). When
FbEq
indicates
1073742081
on page
-
44.24
1 = 1
1 = 1
44.24
0
1
1 = 1 min
1 = 1 min
1
2
3
4