ABB ACS850 Firmware Manual page 227

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

Code
Alarm
(fieldbus code)
2005
MOTOR
TEMPERATURE
(0x4310)
Programmable fault:
31.01 Mot temp1 prot
2006
EMERGENCY OFF
(0xF083)
2007
RUN ENABLE
(0xFF54)
2008
ID-RUN
(0xFF84)
2009
EMERGENCY STOP
(0xF081)
2011
BR OVERHEAT
(0x7112)
2012
BC OVERHEAT
(0x7181)
Cause
Estimated motor temperature
(based on motor thermal
model) has exceeded alarm
limit defined by parameter
31.03 Mot temp1
almLim.
Measured motor temperature
has exceeded alarm limit
defined by parameter
31.03
Mot temp1
almLim.
Drive has received emergency
OFF2 command.
No Run enable signal is
received.
Motor identification run is on.
Motor identification is required. This alarm belongs to normal start-up
Drive has received emergency
stop command (OFF1/OFF3).
Brake resistor temperature has
exceeded alarm limit defined
by parameter
48.07 Br temp
alarmlim.
Brake chopper IGBT
temperature has exceeded
internal alarm limit.
Fault tracing 227
What to do
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters 31.09...31.14).
Check that actual number of sensors
corresponds to value set by parameter
31.02 Mot temp1
src.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
To restart drive, activate Run enable
signal (source selected by parameter
10.11 Run
enable) and start drive.
Check setting of parameter
enable. Switch signal on (e.g. in the
fieldbus Control Word) or check wiring of
selected source.
This alarm belongs to normal start-up
procedure. Wait until drive indicates that
motor identification is completed.
procedure.
Select how motor identification should be
performed, parameter
99.13 Idrun
Start identification routines by pressing
Start key.
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position (or adjust the fieldbus
Control Word accordingly).
Restart drive.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameters
48.01...48.05).
Check alarm limit setting, parameter
48.07 Br temp
alarmlim.
Check that braking cycle meets allowed
limits.
Let chopper cool down.
Check resistor overload protection
function settings (parameters
48.01...48.05).
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
10.11 Run
mode.