48 Program features
WARNING! As the thermistor input on the JCU Control Unit is not insulated
according to IEC 60664, the connection of the motor temperature sensor
requires double or reinforced insulation between motor live parts and the
sensor. If the assembly does not fulfil the requirement,
- the I/O board terminals must be protected against contact and must not be
connected to other equipment
or
- the temperature sensor must be isolated from the I/O terminals.
The figure below shows a motor temperature measurement when thermistor input TH
is used.
One PTC or KTY84 sensor
Motor
T
Three PTC sensors
Motor
T
T
For encoder interface module FEN-xx connection, see the User's Manual of the
appropriate encoder interface module.

Settings

Parameter group
31 Mot therm prot

Timers

It is possible to define four different daily or weekly time periods. The time periods can
be used to control four different timers. The on/off statuses of the four timers are
indicated by bits 0...3 of parameter
be connected to any parameter with a bit pointer setting (see page 63). In addition, bit
4 of parameter
06.14
10 nF
10 nF
T
(page 145).
06.14 Timed func
is on if any one of the four timers is on.
JCU Control Unit
TH
AGND
JCU Control Unit
TH
AGND
stat, from where the signal can