No.
Name/Value
13.29
AI6 max scale
-32768.000 ...
32768.000
13.30
AI6 min scale
-32768.000 ...
32768.000
13.31
AI tune
No action
AI1 min tune
AI1 max tune
AI2 min tune
AI2 max tune
13.32
AI superv func
No
Fault
Description
Defines the real value that corresponds to the maximum
analogue input AI6 value defined by parameter
max.
13.29
13.28
Real value corresponding to maximum AI6 value.
Defines the real value that corresponds to the minimum
analogue input AI6 value defined by parameter
min. See the drawing at parameter
Real value corresponding to minimum AI6 value.
Triggers the AI tuning function.
Connect the signal to the input and select the appropriate
tuning function.
AI tune is not activated.
Current analogue input AI1 signal value is set as minimum
value of AI1 into parameter
back to
No action
automatically.
Current analogue input AI1 signal value is set as maximum
value of AI1 into parameter
back to
No action
automatically.
Current analogue input AI2 signal value is set as minimum
value of AI2 into parameter
back to
No action
automatically.
Current analogue input AI2 signal value is set as maximum
value of AI2 into parameter
back to
No action
automatically.
Selects how the drive reacts when analogue input signal limit
is reached. The limit is selected by parameter
cw.
No action taken.
The drive trips on an AI SUPERVISION fault.
13.27 AI6
AI (scaled)
AI (mA/V)
13.27
13.30
13.28 AI6
13.29 AI6 max
13.03 AI1
min. The value reverts
13.02 AI1
max. The value reverts
13.08 AI2
min. The value reverts
13.07 AI2
max. The value reverts
13.33 AI superv
Parameters 95
FbEq
1000 = 1
scale.
1000 = 1
0
1
2
3
4
0
1