ABB ACS850 Firmware Manual page 126

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

126 Parameters
No.
Name/Value
22.03
Dec time1
0.000 ... 1800.000
s
22.04
Acc time2
0.000 ... 1800.000
s
22.05
Dec time2
0.000 ... 1800.000
s
Description
Defines deceleration time 1 as the time required for the speed
to change from the speed value defined by parameter
Speed scaling
to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference
signal.
If the reference changes faster than the set deceleration rate,
the motor speed will follow the deceleration rate.
If the deceleration time is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits. If there is any doubt about the deceleration
time being too short, ensure that the DC overvoltage control
is on (parameter
47.01 Overvolt
Note: If a short deceleration time is needed for a high inertia
application, the drive should be equipped with an electric
braking option e.g. with a brake chopper (built-in) and a brake
resistor.
Deceleration time 1.
Defines acceleration time 2. See parameter
Acceleration time 2.
Defines deceleration time 2. See parameter
Deceleration time 2.
19.01
ctrl).
22.02 Acc
time1.
22.03 Dec
time1.
FbEq
1000 = 1 s
1000 = 1 s
1000 = 1 s

Advertisement

Table of Contents
loading