74 Parameters
No.
Name/Value
06.02
Status word2
Bit
Name
0
Start act
1
Stop act
2
Ready relay 1 = Ready to function: run enable signal on, no fault, emergency stop signal
3
Modulating 1 = Modulating: IGBTs are controlled, ie. the drive is RUNNING.
4
Ref running 1 = Normal operation is enabled. Running. Drive follows the given
5
Jogging
6
Off1
7
Start inh
mask
8
Start inh
nomask
9
Chrg rel
closed
10
Sto act
11
Reserved
12
Ramp in 0
13
Ramp hold 1 = Ramp Function Generator output is held.
14
Ramp out 0 1 = Ramp Function Generator output is forced to zero.
15...31 Reserved
Description
Status word 2 sent to the master.
Information
1 = Drive start command is active.
0 = Drive start command is inactive.
1 = Drive stop command is active.
0 = Drive stop command is inactive.
off, no ID run inhibition. Connected by default to DIO1 by par.
out
src.
0 = Not ready to function.
0 = No modulation: IGBTs are not controlled.
reference.
0 = Normal operation is disabled. Drive is not following the given reference
(eg. in magnetization phase drive is modulating).
1 = Jogging function 1 or 2 is active.
0 = Jogging function is inactive.
1 = Emergency stop OFF1 is active.
0 = Emergency stop OFF1 is inactive.
1 = Maskable (by par.
12.01 Start
0 = No maskable start inhibit is active.
1 = Non-maskable start inhibit is active.
0 = No non-maskable start inhibit is active.
1 = Charging relay is closed.
0 = Charging relay is open.
1 = Safe Torque Off function is active. See parameter
0 = Safe Torque Off function is inactive.
1 = Ramp Function Generator input is forced to zero.
0 = Normal operation.
0 = Normal operation.
0 = Normal operation.
inhibit) start inhibit is active.
30.07 Sto
FbEq
-
14.03 DIO1
diagnostic.