Code
Fault
(fieldbus code)
0050
ENCODER 1 CABLE
(0x7389)
Programmable fault:
90.05 Enc cable fault
0051
ENCODER 2 CABLE
(0x738A)
Programmable fault:
90.05 Enc cable fault
0052
D2D CONFIG
(0x7583)
0053
D2D COMM
(0x7520)
Programmable fault:
57.02 Comm loss func
0054
D2D BUF OVLOAD
(0x7520)
Programmable fault:
90.05 Enc cable fault
0055
TECH LIB
(0x6382)
0056
TECH LIB CRITICAL
(0x6382)
0057
FORCED TRIP
(0xFF90)
0058
FB PAR ERROR
(0x6320)
0059
STALL
(0x7121)
Programmable fault:
30.09 Stall function
0060
LOAD CURVE
(0x2312)
Programmable fault:
34.01 Overload func
34.02 Underload func
Cause
Encoder 1 cable fault detected. Check cable between FEN-xx interface
Encoder 2 cable fault detected. Check cable between FEN-xx interface
Configuration of the drive-to-
drive link has failed for a
reason other than those
indicated by alarm A-2042, for
example start inhibition is
requested but not granted.
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
On a follower drive: The drive
has not received new
reference 1 and/or 2 for five
consecutive reference
handling cycles.
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Resettable fault generated by
a technology library.
Permanent fault generated by
a technology library.
Generic Drive Communication
Profile trip command.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Overload or underload limit
has been exceeded.
/
Fault tracing 239
What to do
and encoder 1. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
90.10 Enc par
refresh.
and encoder 2. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
90.10 Enc par
refresh.
Contact your local ABB representative.
Check that all drives that are polled
(parameters
57.04 Follower mask 1
57.05 Follower mask
2) on the drive-to-
drive link are powered, properly
connected to the link, and have the
correct node address.
Check the drive-to-drive link wiring.
Check the settings of parameters
Ref 1 src
and
57.07 Ref 2
master drive.
Check the drive-to-drive link wiring.
Contact your local ABB representative.
Refer to the documentation of the
technology library.
Refer to the documentation of the
technology library.
Check PLC status.
Check PLC programming.
Check settings of parameter group
Fieldbus.
Check motor load and drive ratings.
Check fault function parameters.
Check the settings of the parameters in
group
34 User load
curve.
and
57.06
src) on the
50