ABB ACS850 Firmware Manual page 163

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

No.
Name/Value
DI3
DI4
DI5
DI6
DIO4
DIO5
DIO6
Const
Pointer
36.02
Timers mode
Bit
Function
0
Timer1 mode
0 = Daily
1 = Weekly
1
Timer2 mode
0 = Daily
1 = Weekly
2
Timer3 mode
0 = Daily
1 = Weekly
3
Timer4 mode
0 = Daily
1 = Weekly
36.03
Start time1
00:00:00 ...
24:00:00
36.04
Stop time1
00:00:00 ...
24:00:00
36.05
Start day1
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
36.06
Stop day1
Monday
Tuesday
Description
Digital input DI3 (as indicated by
Digital input DI4 (as indicated by
Digital input DI5 (as indicated by
Digital input DI6 (as indicated by
Digital input/output DIO4 (as indicated by
bit 3).
Digital input/output DIO5 (as indicated by
bit 4).
Digital input/output DIO6 (as indicated by
bit 5).
Bit pointer setting (see
Terms and abbreviations
Specifies whether the time periods defined by parameters
36.03 Start time1
...
36.18 Stop day4
weekly.
Defines the start time for time period 1.
Start time for time period 1.
Defines the stop time for time period 1.
Stop time for time period 1.
Defines the week day on which time period 1 begins.
Time period 1 starts on Monday.
Time period 1 starts on Tuesday.
Time period 1 starts on Wednesday.
Time period 1 starts on Thursday.
Time period 1 starts on Friday.
Time period 1 starts on Saturday.
Time period 1 starts on Sunday.
Defines the week day on which time period 1 ends.
Time period 1 ends on Monday.
Time period 1 ends on Tuesday.
Parameters 163
02.01 DI
status, bit 2).
02.01 DI
status, bit 3).
02.01 DI
status, bit 4).
02.01 DI
status, bit 5).
02.03 DIO
status,
02.03 DIO
status,
02.03 DIO
status,
on page 63). -
are valid daily or
FbEq
1073873409
1073938945
1074004481
1074070017
1073938947
1074004483
1074070019
1 = 1 s
(24:00:00 =
86400)
1 = 1 s
(24:00:00 =
86400)
1
2
3
4
5
6
7
1
2

Advertisement