154 Parameters
No.
Name/Value
Pointer
33.11
Superv3 hi
-32768.00 ...
32768.00
33.12
Superv3 lo
-32768.00 ...
32768.00
34

34 User load curve

34.01
Overload func
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Input value sel (Input value selection)
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
2
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm when the curve is exceeded.
3
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault when the curve is exceeded.
4
Ena lim integ (Enable limit integration)
0 = Disabled
1 = Enabled: Integration time defined by parameter
the supervision is evoked, the current or torque is limited by the upper boundary of the
load curve.
5
Ena lim always (Enable limit always)
0 = Disabled
1 = Enabled: The current or torque is always limited by the upper boundary of the load
curve.
Description
Value pointer setting (see
63).
Selects the upper limit for supervision 3. See parameter
Superv3
func.
Upper limit for supervision 3.
Selects the lower limit for supervision 3. See parameter
Superv3
func.
Lower limit for supervision 3.
Definition of user load curve. See also section
curve
on page 50.
Configures the supervision of the upper boundary of the user
load curve.
Terms and abbreviations
User load
34.18 Load integ time
FbEq
on page
-
33.09
100 = 1
33.09
100 = 1