97.11
Lm user SI
0.00 ...100000.00
mH
97.12
SigL user SI
0.00 ...100000.00
mH
97.13
Ld user SI
0.00 ...100000.00
mH
97.14
Lq user SI
0.00 ...100000.00
mH
99

99 Start-up data

99.01
Language
English
Deutsch
Italiano
Suomi
99.04
Motor type
AM
PMSM
99.05
Motor ctrl mode
DTC
Description
Defines the main inductance L
Note: This parameter is valid only for asynchronous motors.
Main inductance.
Defines the leakage inductance
Note: This parameter is valid only for asynchronous motors.
Leakage inductance.
Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
Direct axis inductance.
Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
Quadrature axis inductance.
Language selection, motor configuration and ID run settings.
Selects the language of the control panel displays.
Note: Not all languages listed below are necessarily
supported.
English.
German.
Italian.
Finnish.
Selects the motor type.
Note: This parameter cannot be changed while the drive is
running.
Asynchronous motor. Three-phase AC induction motor with
squirrel cage rotor.
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal BackEMF
voltage.
Selects the motor control mode.
Direct torque control. This mode is suitable for most
applications.
Note: Instead of direct torque control, use scalar control
• with multimotor applications 1) if the load is not equally
shared between the motors, 2) if the motors are of different
sizes, or 3) if the motors are going to be changed after the
motor identification (ID run),
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive,
• if the drive is used with no motor connected (for example,
for test purposes),
• if the drive runs a medium-voltage motor through a step-up
transformer.
of the motor model.
M
σ
L
.
S
Parameters 199
FbEq
100 = 1 mH
100 = 1 mH
100 = 1 mH
100 = 1 mH
2057
1031
1040
1035
0
1
0