216 Additional parameter data
No.
Name
30.12 Stall time
31 Mot therm prot
31.01 Mot temp1 prot
31.02 Mot temp1 src
31.03 Mot temp1 almLim
31.04 Mot temp1 fltLim
31.05 Mot temp2 prot
31.06 Mot temp2 src
31.07 Mot temp2 almLim
31.08 Mot temp2 fltLim
31.09 Mot ambient temp
31.10 Mot load curve
31.11 Zero speed load
31.12 Break point
31.13 Mot nom tempRise
31.14 Mot therm time
32 Automatic reset
32.01 Autoreset sel
32.02 Number of trials
32.03 Trial time
32.04 Delay time
33 Supervision
33.01 Superv1 func
33.02 Superv1 act
33.03 Superv1 hi
33.04 Superv1 lo
33.05 Superv2 func
33.06 Superv2 act
33.07 Superv2 hi
33.08 Superv2 lo
33.09 Superv3 func
33.10 Superv3 act
33.11 Superv3 hi
33.12 Superv3 lo
34 User load curve
34.01 Overload func
34.02 Underload func
34.03 Load freq1
34.04 Load freq2
34.05 Load freq3
Data
Type
len.
UINT32
16
enum
16
enum
16
INT32
16
INT32
16
enum
16
enum
16
INT32
16
INT32
16
INT32
16
INT32
16
INT32
16
INT32
16
INT32
16
INT32
16
Pb
16
UINT32
16
UINT32
16
UINT32
16
enum
16
Val pointer
32
REAL
32
REAL
32
enum
16
Val pointer
32
REAL
32
REAL
32
enum
16
Val pointer
32
REAL
32
REAL
32
Pb
16
Pb
16
REAL
16
REAL
16
REAL
16
Range
0...3600
0...2
0...12
0...200
0...200
0...2
0...12
0...200
0...200
-60...100
50...150
50...150
0.01...500
0...300
100...10000
0b000000...0b111111
0...5
1...600
0...120
0...4
-
-32768...32768
-32768...32768
0...4
-
-32768...32768
-32768...32768
0...4
-
-32768...32768
-32768...32768
0b000000...0b111111
0b0000...0b1111
1...500
1...500
1...500
Default
Unit
(Factory macro)
s
20 s
-
No
-
Estimated
°C
90 °C
°C
110 °C
-
No
-
Estimated
°C
90 °C
°C
110 °C
°C
20 °C
%
100%
%
100%
Hz
45.00 Hz
°C
80 °C
s
256 s
-
0b000000
-
0
s
30.0 s
s
0.0 s
-
Disabled
-
Speed rpm
-
0.00
-
0.00
-
Disabled
-
Current
-
0.00
-
0.00
-
Disabled
-
Torque
-
0.00
-
0.00
-
0b000000
-
0b0000
Hz
5 Hz
Hz
25 Hz
Hz
43 Hz

Advertisement

Table of Contents
loading

Table of Contents