User Motor Par - ABB ACS850 Firmware Manual

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

198 Parameters
No.
Name/Value
97

97 User motor par

97.01
Use given params
0
1
97.02
Rs user
0.00000 ... 0.50000
p.u.
97.03
Rr user
0.00000 ... 0.50000
p.u.
97.04
Lm user
0.00000 ...
10.00000 p.u.
97.05
SigmaL user
0.00000 ... 1.00000
p.u.
97.06
Ld user
0.00000 ...
10.00000 p.u
97.07
Lq user
0.00000 ...
10.00000 p.u
97.08
Pm flux user
0.00000 ... 2.00000
p.u
97.09
Rs user SI
0.00000 ...
100.00000 ohm
97.10
Rr user SI
0.00000 ...
100.00000 ohm
Description
Motor values supplied by the user that are used in the motor
model.
Activates the motor model parameters 97.02...97.14.
Notes:
Parameter value is automatically set to zero when ID run is
selected by parameter
99.13 Idrun
parameters
97.02...97.14
characteristics identified during the ID run.
This parameter cannot be changed while the drive is running.
Parameters
97.02...97.14
The values of parameters
model.
Defines the stator resistance R
Stator resistance in per unit.
Defines the rotor resistance R
Note: This parameter is valid only for asynchronous motors.
Rotor resistance in per unit.
Defines the main inductance L
Note: This parameter is valid only for asynchronous motors.
Main inductance in per unit.
Defines the leakage inductance
Note: This parameter is valid only for asynchronous motors.
Leakage inductance in per unit.
Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
Direct axis inductance in per unit.
Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
Quadrature axis inductance in per unit.
Defines the permanent magnet flux.
Note: This parameter is valid only for permanent magnet
motors.
Permanent magnet flux in per unit.
Defines the stator resistance R
Stator resistance.
Defines the rotor resistance R
Note: This parameter is valid only for asynchronous motors.
Rotor resistance.
mode. The values of
are updated according to the motor
inactive.
97.02...97.14
are used in the motor
of the motor model.
S
of the motor model.
R
of the motor model.
M
σ
L
.
S
of the motor model.
S
of the motor model.
R
FbEq
0
1
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 p.u.
100000 =
1 ohm
100000 =
1 ohm

Advertisement

Table of Contents
loading

Table of Contents