13 Analogue inputs

13.01
AI1 filt time
0.000 ... 30.000 s
13.02
AI1 max
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
13.03
AI1 min
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
Description
Analog input signal processing.
Defines the filter time constant for analogue input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
Filter time constant.
Defines the maximum value for analogue input AI1. The input
type is selected with jumper J1 on the JCU Control Unit.
Maximum AI1 value.
Defines the minimum value for analogue input AI1. The input
type is selected with jumper J1 on the JCU Control Unit.
Minimum AI1 value.
t
)
Parameters 89
FbEq
1000 = 1 s
1000 = 1 unit
1000 = 1 unit