Hand/Auto Macro - ABB ACS850 Firmware Manual

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

54 Application macros

Hand/Auto macro

The Hand/Auto macro is suited for speed control applications where two external
control devices are used.
The drive is speed-controlled from the external control locations EXT1 and EXT2.
The selection between the control locations is done through digital input DI3.
The start/stop signal for EXT1 is connected to DI1 while running direction is
determined by DI2. For EXT2, start/stop commands are given through DI6, the
direction through DI5.
The reference signals for EXT1 and EXT2 are connected to analog inputs AI1 and
AI2 respectively.
A constant speed (300 rpm) can be activated through DI4.
Default parameter settings for Hand/Auto macro
Below is a listing of default parameter values that differ from those listed in chapter
Additional parameter data
Parameter
No.
Name
10.01
Ext1 start func
10.03
Ext1 start in2
10.04
Ext2 start func
10.05
Ext2 start in1
10.06
Ext2 start in2
10.10
Fault reset sel
12.01
Ext1/Ext2 sel
13.05
AI1 min scale
13.09
AI2 max scale
13.10
AI2 min scale
21.02
Speed ref2 sel
21.04
Speed ref1/2 sel
26.02
Const speed sel1
26.06
Const speed1
(page 203).
Hand/Auto macro
default
In1St In2Dir
DI2
In1St In2Dir
DI6
DI5
C.FALSE
DI3
0.000
1500.000
0.000
AI2 scaled
DI3
DI4
300 rpm