Setting up communication through a fieldbus adapter
module
Before configuring the drive for fieldbus control, the adapter module must be
mechanically and electrically installed according to the instructions given in the
User's Manual of the appropriate fieldbus adapter module.
The communication between the drive and the fieldbus adapter module is activated
by setting parameter
must also be set. See the table below.
Parameter
COMMUNICATION INITIALISATION AND SUPERVISION (see also page 182)
50.01 Fba enable
50.02 Comm loss
func
50.03 Comm loss t
out
50.04 Fba ref1
modesel
and
50.05
Fba ref2 modesel
ADAPTER MODULE CONFIGURATION (see also page 183)
51.01 FBA type
51.02 FBA par2
• • •
51.26 FBA par26
51.27 FBA par
refresh
51.28 Par table ver
51.29 Drive type
code
50.01 Fba enable
to Enable. The adapter-specific parameters
Setting for
fieldbus control
(1)
Enable
(0)
No
(1)
Fault
(2)
Spd ref Safe
(3)
Last speed
0.3...6553.5 s
(0)
Raw data
(1)
Torque
(2)
Speed
These parameters are adapter module-specific. For more
information, see the User's Manual of the fieldbus adapter module.
Note that not all of these parameters are necessarily used.
(0)
Done
(1)
Refresh
Function/Information
Initialises communication between drive
and fieldbus adapter module.
Selects how the drive reacts upon a fieldbus
communication break.
Defines the time between communication
break detection and the action selected with
parameter
50.02 Comm loss
Defines the fieldbus reference scaling.
When
Raw data
is selected, see also
parameters 50.06...50.11.
Displays the type of the fieldbus adapter
module.
Validates any changed adapter module
configuration parameter settings.
Displays the parameter table revision of the
fieldbus adapter module mapping file stored
in the memory of the drive.
Displays the drive type code of the fieldbus
adapter module mapping file stored in the
memory of the drive.
Fieldbus control 245