14 Start-up
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
ABB Motors
3
motor
Hz
kW
V
690 Y
30
50
400 D
50
660 Y
50
380 D
50
50
415 D
440 D
60
Cat. no
3GAA 202 001 - ADA
6312/C3
Permanent magnet motor nameplate example:
At least parameters
control
(99.05 Motor ctrl mode
accuracy can be achieved by setting also parameters
99.11...99.12.
• motor nominal current
Allowed range: approximately 1/6 × I
drive (0...2 × I
2nd
Scalar). With multimotor drives, see page 16.
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
r/min
A
cos
1475
32.5
0.83
1475
56
0.83
30
1470
34
0.83
30
30
1470
59
0.83
1475
54
0.83
30
35
1770
59
0.83
6210/C3
IEC 34-1
99.06...99.10
must be set with DTC
= DTC). Better control
2n
if parameter
99.05 Motor ctrl mode
Note: Set the motor data to
exactly the same value as
on the motor nameplate.
For example, if the motor
nominal speed is 1470 rpm
on the nameplate, setting
the value of parameter
99.09 Mot nom speed
IP 55
IA/IN t E/s
1500 rpm results in wrong
operation of the drive.
380 V
mains
voltage
180
99.06 Mot nom current
... 2 × I
of the
2n
=
to