ABB ACS850 Firmware Manual page 93

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

No.
Name/Value
13.19
AI4 max scale
-32768.000 ...
32768.000
13.20
AI4 min scale
-32768.000 ...
32768.000
13.21
AI5 filt time
0.000 ... 30.000 s
13.22
AI5 max
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
13.23
AI5 min
-22.000 ... 22.000
mA or
-11.000 ... 11.000 V
Description
Defines the real value that corresponds to the maximum
analogue input AI4 value defined by parameter
max.
13.19
13.18
Real value corresponding to maximum AI4 value.
Defines the real value that corresponds to the minimum
analogue input AI4 value defined by parameter
min. See the drawing at parameter
Real value corresponding to minimum AI4 value.
Defines the filter time constant for analogue input AI5. See
parameter
13.01 AI1 filt
Filter time constant.
Defines the maximum value for analogue input AI5. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
AI5 maximum value.
Defines the minimum value for analogue input AI5. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
AI5 minimum value.
13.17 AI4
AI (scaled)
AI (mA/V)
13.17
13.20
13.18 AI4
13.19 AI4 max
time.
Parameters 93
FbEq
1000 = 1
scale.
1000 = 1
1000 = 1 s
1000 = 1 unit
1000 = 1 unit

Advertisement