45 Energy optimising

45.01
Energy optim
Disable
Enable
45.02
Energy tariff1
0.00 ...
21474836.47
45.06
E tariff unit
Local
Eur
Usd
45.08
Pump ref power
00.0... 1000.0%
45.09
Energy reset
Done
Reset
Description
Pre-selectable alarm for the drive run time counter.
Sets the limit for the energy counter. The counter monitors
signal
01.24 kWh inverter
reaches the limit, the alarm specified by parameter
kWh inv alm sel
is given.
Alarm limit for the energy counter.
Selects the alarm for the energy counter.
Pre-selectable alarm for the energy counter.
Pre-selectable alarm for the energy counter.
Pre-selectable alarm for the energy counter.
Pre-selectable alarm for the energy counter.
Pre-selectable alarm for the energy counter.
Energy optimization settings.
Enables/disables energy optimization function. The function
optimizes the flux so that total energy consumption and motor
noise level are reduced when the drive operates below the
nominal load. The total efficiency (motor and drive) can be
improved by 1...10% depending on load torque and speed.
Energy optimization disabled.
Energy optimization enabled.
Price of energy per kWh. Used for reference when savings
are calculated. See parameters
Saved amount
and
01.37 Saved
Price of energy per kWh.
Specifies the currency used for the savings calculation.
The currency is determined by the setting of parameter
Language.
Euro.
US dollar.
Pump power when connected directly to supply. Used for
reference when energy savings are calculated. See
parameters
01.35 Saved
01.37 Saved
CO2.
Pump power in percent of nominal motor power.
Resets the energy counters
Saved amount
and
01.37 Saved
Reset not requested (normal operation).
Reset energy counters. The value reverts automatically to
Done.
(see page 64). When the signal
01.35 Saved
energy,
CO2.
energy,
01.36 Saved amount
01.35 Saved
energy,
CO2.
Parameters 179