Automatic Reset; Supervision - ABB ACS850 Firmware Manual

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

No.
Name/Value
32

32 Automatic reset

32.01
Autoreset sel
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI min
4
Line converter
5
External fault
32.02
Number of trials
0 ... 5
32.03
Trial time
1.0 ... 600.0 s
32.04
Delay time
0.0 ... 120.0 s
33

33 Supervision

33.01
Superv1 func
Disabled
Low
High
Abs Low
Abs High
33.02
Superv1 act
Speed rpm
Speed %
Frequency
Current
Current %
Description
Defines conditions for automatic fault resets.
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The bits of the binary number correspond to the following
faults:
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
time.
Number of automatic resets.
Defines the time for the automatic fault reset function. See
parameter
32.02 Number of
Time for automatic resets.
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
Autoreset
sel.
Resetting delay.
Configuration of signal supervision.
Selects the mode of supervision 1.
Supervision 1 not in use.
When the signal selected by parameter
falls below the value of parameter
06.13 Superv status
is activated.
When the signal selected by parameter
exceeds the value of parameter
06.13 Superv status
is activated.
When the absolute value of the signal selected by parameter
33.02 Superv1 act
falls below the value of parameter
Superv1
lo, bit 0 of
06.13 Superv status
When the absolute value of the signal selected by parameter
33.02 Superv1 act
exceeds the value of parameter
Superv1
hi, bit 0 of
06.13 Superv status
Selects the signal to be monitored by supervision 1. See
parameter
33.01 Superv1
01.01 Motor speed rpm
01.02 Motor speed %
(see page 64).
01.03 Output frequency
01.04 Motor current
(see page 64).
01.05 Motor current %
(see page 64).
32.03 Trial
trials.
32.01
33.02 Superv1 act
33.04 Superv1
33.02 Superv1 act
33.03 Superv1
hi, bit 0 of
is activated.
is activated.
func.
(see page 64).
(see page 64).
Parameters 151
FbEq
1 = 1
10 = 1 s
10 = 1 s
0
1
lo, bit 0 of
2
3
33.04
4
33.03
1073742081
1073742082
1073742083
1073742084
1073742085