ABB ACS850 Firmware Manual page 148

Standard control program
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

148 Parameters
No.
Name/Value
KTY 2nd FEN
PTC JCU
PTC 1st FEN
PTC 2nd FEN
Pt100 JCU x1
Pt100 JCU x2
Pt100 JCU x3
Pt100 Ext x1
Pt100 Ext x2
Pt100 Ext x3
31.07
Mot temp2 almLim
0 ... 200 °C
31.08
Mot temp2 fltLim
0 ... 200 °C
31.09
Mot ambient temp
-60 ... 100 °C
Description
The temperature is supervised using a KTY84 sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
Note: This selection does not apply to FEN-01.
The temperature is supervised using 1...3 PTC sensors
connected to drive thermistor input TH.
The temperature is supervised using a PTC sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 1 is used for the
temperature supervision.
The temperature is supervised using a PTC sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
The temperature is supervised using a Pt100 sensor
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
The temperature is supervised using two Pt100 sensors
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
The temperature is supervised using three Pt100 sensors
connected to analog input AI1 and analog output AI1 on the
JCU Control Unit of the drive.
The temperature is supervised using a Pt100 sensor
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
The temperature is supervised using two Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
The temperature is supervised using three Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
Defines the alarm limit for the motor thermal protection 2
(when parameter
31.05 Mot temp2 prot
or Fault).
Motor overtemperature alarm limit.
Defines the fault limit for the motor thermal protection 2 (when
parameter
31.05 Mot temp2 prot
Motor overtemperature fault limit.
Defines the ambient temperature for the thermal protection
mode.
Ambient temperature.
is set to either
Alarm
is set to Fault).
FbEq
3
4
5
6
7
8
9
10
11
12
1 = 1 °C
1 = 1 °C
1 = 1 °C

Advertisement