Settings

Parameter group

Load analyzer

The load analyzer can be used for analyzing the customer's process and sizing the
drive and the motor.
The peak value is logged at 2 ms level, and the distribution loggers are updated on
0.2 s (200 ms) time level. Three different values can be logged:
1. The measured current is logged continuously. The distribution as a percentage of
the maximum current is shown in ten classes.
2. One signal in group 1 can be logged for the peak (maximum) value. The peak
value of the signal, peak time (time when the peak value was detected) as well
the frequency, current and DC voltage at the peak time are shown.
3. One signal in group 1 can be logged for amplitude distribution. The base value
(100% value) can be set by the user.
Logger 1 cannot be reset. Loggers 2 and 3 can be reset by a user-defined method.
They are also reset if either of the signals or the peak value filter time is changed.
Settings
Parameter
Group
64 LOAD
ANALYZER,
parameters
6401...6405

Diagnostics

Actual signal
Group
64 LOAD
ANALYZER,
parameters
6406...6433
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
46 PUMP CLEANING
Additional information
Load analyzer settings
Additional information
Load analyzer results
Program features 145