PRE-OPERATION PROCEDURES

5.2
Pre-Operation Procedures
This section describes the outline procedure to be taken before operation.
5.2.1

Consideration before configuring the EtherNet/IP network

Consider the items described in this section before configuring the EtherNet/IP network,
and start up the system according to the flowchart in Section 5.2.2.
(1) Network configuration and IP address
Consider network configuration
and IP Addresses.
IP Address: 192.168.0.1
(2) Tag types and data sizes
Consider the types, names, and data sizes of the tags.
When using auto refresh, consider auto refresh
target devices.
QCPU
W0 to W4
5 Words
9 Words
W5 to WD
W100 to W107
8 Words
12 Words
W108 to W113
Figure 5.2 Consideration of tag types and data size (for Class1 Tag communication)
Remark
Figure 5.1 Consideration of IP address
System 1 (192.168.0.1)
Consumer Tag (5 Words)
Consumer Tag (9 Words)
Producer Tag (8 Words)
Producer Tag (12 Words)
For details of tag types, refer to the following.
Section 4.2 Tag Communication Function
5.2.1 Consideration before configuring the EtherNet/IP network
IP Address: 192.168.0.2
Switching
hub
IP Address: 192.168.0.3
System 2 (192.168.0.2)
Consumer Tag (8 Words)
Consumer Tag (12 Words)
Producer Tag (5 Words)
System 3 (192.168.0.3)
Consumer Tag (8 Words)
Consumer Tag (12 Words)
Producer Tag (9 Words)
5.2 Pre-Operation Procedures
1
2
3
4
5
6
7
8
5
- 2