Advertisement

5
PRE-OPERATION PROCEDURES
5.5

Setting from GX Works2

This section describes the GX Works2 settings required to operate the EtherNet/IP
module. When using GX Developer, refer to the following.
5.5.1
Set the Tag communication status for a CPU stop error.
For details of Tag communication for a CPU stop error, refer to the following.
Type
Model Name
Points
Start XY
Error Time Output Mode
5
- 15
5.5 Setting from GX Works2

5.5.1 Intelligent function module detailed setting

Appendix 3 When Using GX Developer
Intelligent function module detailed setting
Section 4.3 Tag Communication Status Setting Function for CPU Stop Error
1) Double-click "PLC Parameter" in the project window in GX Works2.
2) Click the "I/O Assignment" tab.
3) Set the following items for the slot where the EtherNet/IP module is mounted,
and then click
Figure 5.12 "I/O Assignment"
Table 5.7 Setting items on the "I/O Assignment" tab
Item
Select "Intelligent".
Enter the model name of the module.
Select "32points".
Enter the start I/O number of the EtherNet/IP module.
4) Clicking
Detailed Setting
Setting" window.
Refer to the following and complete the setting.
Figure 5.13 "Intelligent Function Module Detailed Setting"
Table 5.8 Setting description in "Intelligent Function Module Detailed Setting"
Item
Clear: Stops Tag communication when a CPU stop error occurred. (default)
Hold: Continues Tag communication when a CPU stop error occurred.
.
Detailed Setting
Description
displays the "Intelligent Function Module Detailed
Setting for a CPU stop error
Description