Calibrate and Configure the Position Transmitter

1. Install the latest version of the communication software on the user interface tool.
Note
This may include an FDI package or DD. Contact your
information on locating the necessary files.
2. If you haven't already done so, perform the Electrical Connections procedure on page 12.
3. Remove the cover to apply electrical power to the position transmitter.
4. Ensure the LED is solid green prior to calibrating the instrument.
Note
If the LED is not green, check the magnet assembly position and adjust as needed. Ensure the instrument is in service. If
performing the calibration procedure after a failed calibration the LED will be blinking red. Cycle instrument power before
attempting another calibration.
5. Proceed to the calibration procedure on the next page.
Note
The TALK terminals are located under the transmitter cover.
Note
In order to perform calibration and/or configuration procedures, the configuration lock switch (shown in figure 9) must be in the
unprotected position (  ) and the instrument must be In Service.
Once calibration and configuration is complete, set the configuration lock switch to the protected position (  ) to prevent
configuration and calibration changes to the instrument.