Ce Compliance - Danfoss VLTAutomationDrive FC 360 Quick Manual

Table of Contents

Advertisement

Specifications

8.3.3 CE Compliance

Fuses or Circuit Breakers are mandatory to comply with IEC
60364. Danfoss recommend using a selection of the
following.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 480 V depending
on the frequency converter voltage rating. With the proper
fusing the frequency converter short circuit current rating
(SCCR) is 100,000 Arms.
Frame Size
Power [kW]
0.37-1.1
J1
1.5
2.2
3.0
J2
4.0
5.5
J3
7.5
J4
11-15
18.5
J5
22
30
J6
37
45
55
J7
75
Table 8.4 CE Fuse, 380-480 V, Frame Sizes J1-J7
The circuit breakers below are suitable for use on a circuit
capable of delivering 35,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
the proper fusing the frequency converter short circuit
current rating (SCCR) is 35,000 Arms.
Frame Size
Power [kW]
0.37-1.1
J1
1.5
2.2
3.0
J2
4.0
5.5
J3
7.5
J4
11-15
18.5
J5
22
30
J6
37
45
55
J7
75
Table 8.5 CE Circuit Breakers, 380-480 V, Frame Sizes J1-J7
®
VLT
AutomationDrive FC 360 Quick Guide
UL Compliance
Fuses or Circuit Breakers are mandatory to comply with
NEC 2009. We recommend using a selection of the
following
The circuit breakers below are suitable for use on a circuit
capable of delivering 100,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
the proper fusing the drive Short Circuit Current Rating
(SCCR) is 100,000 Arms.
The circuit breakers below are suitable for use on a circuit
capable of delivering 35,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
gG
the proper fusing the frequency converter short circuit
current rating (SCCR) is 35,000 Arms.
10
Frame Size
25
32
50
80
160
250
Table 8.6 UL Fuse, 380-480 V, Frame Sizes J1-J7
Frame Size
EATON
Moller
PKZM0-16
NZMN-1-A-25
NZMN-1-A-32
NZMN-1-A-50
NZMN-1-A-80
NZMN-1-A-160
NZMN-1-A-250
Table 8.7 UL Circuit Breakers, 380-480 V, Frame Sizes J1-J7
®
MG06A102 - VLT
is a registered Danfoss trademark
Power [kW]
0.37-1.1
J1
1.5
2.2
3.0
J2
4.0
5.5
J3
7.5
J4
11-15
18.5
J5
22
30
J6
37
45
55
J7
75
Power [kW]
0.37-1.1
J1
1.5
2.2
3.0
J2
4.0
5.5
J3
7.5
J4
11-15
18.5
J5
22
30
J6
37
45
55
J7
75
Bussmann
FRS-R-16
FRS-R-25
FRS-R-30
FRS-R-50
FRS-R-80
FRS-R-150
FRS-R-250
EATON
XTPR016BC1+XTPAXLSA
NZMN-2-A-25-NA
NZMN-2-A-32-NA
NZMN-2-A-50-NA
NZMN-2-A-80-NA
NZMN-2-A-160-NA
NZMN-2-A-250-NA
43
8
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents