Specifications
10.3 Fuse Specifications
10.3.1 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC
60364. Danfoss recommend using a selection of the
following.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical) with the following
voltage
10.3.2 Fuse Tables
Enclosure
Power [kW]
A1
-
A2
0.25-2.2
A3
3.0-3.7
A4
0.25-2.2
A5
0.25-3.7
B1
5.5-11
B2
15
B3
5.5-11
B4
15-18
C1
18.5-30
C2
37-45
C3
22-30
C4
37-45
Table 10.12 200-240 V, Frame Sizes A, B and C
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
®
VLT
AQUA Drive
Operating Instructions
Recommended
Recommended
fuse size
gG-10
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-63 (15)
gG-160 (15-18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
®
MG20M902 - VLT
is a registered Danfoss trademark
•
240 V
•
480 V
•
600 V
•
690 V
depending on the drive voltage rating. With the proper
fusing the drive Short Circuit Current Rating (SCCR) is
100,000 Arms.
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
PKZM0-16
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
Max trip level [A]
16
25
25
25
25
63
100
10
50
100
160
250
150
250
73
10
Need help?
Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?
Questions and answers