Bi-Parting/Dual Gate System; Power Requirements - HySecurity SwingSmart DC Series Programming And Operations Manual

Pad-mounted electromechanical swing gate operator with smart dc controller
Table of Contents

Advertisement

Configuring two operators to be a Primary
and Secondary pair is easy with the Smart DC
Controller. There is no need to order a special
model or any adapters. The area of the board
marked Dual Gate employs a 3-wire RS-485 serial
port for communication between primary and
secondary operators. See Figure 54.

POWER REQUIREMENTS

When installing a dual-operator system, the
following must be adhered to:
z An electrical conduit for interconnecting wires
must span between the two operators. The dual
gate communication wires and any low voltage
control wires must be installed in a conduit that
is separate from the high voltage power wires.
See Table 16 and Figure 54.
z Complete the installation of both operators as
separate machines and verify that their basic
functions are correct as solo operators before
interconnecting them.
AC Power
Two operators 115V
Two operators 230V
SENSOR
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
97
| www.hysecurity.com
Table 16. Power Requirements
14 gauge wire
305 ft (95 meters)
1220 ft (370 meters)
Connection for Primary/Secondary pair
Figure 54. Primary-Secondary Pair
SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL
BI - PARTING/DUAL GATE SYSTEM
z External control inputs, vehicle detectors
and entrapment protection sensors may be
connected to either gate operator without
regard to preference.
z Be sure both operators are running the same
software version. The software version is
available on the display by pressing the RESET
button on the operator. The software version
appears beneath the word HYSECURITY. Keep
the most current software loaded. It is available
at www.hysecurity.com. Make it part of your
maintenance routine to check for software
upgrades on a regular basis.
z Both operators can be connected to the same
20A circuit breaker in the main panel. The wire
size affects operator performance. Use the
following chart as a guideline to size wire for
the given distance from the power source to
BOTH operators.
12 gauge wire
500 ft (150 meters)
1950 ft (590 meters)
10 gauge wire
775 ft (240 meters)
3100 ft (940 meters)
USB Port
MX3640-01 REV. D ©2018