Adjusting The Ies Sensitivity - HySecurity SwingSmart DC Series Programming And Operations Manual

Pad-mounted electromechanical swing gate operator with smart dc controller
Table of Contents

Advertisement

ADJUSTING THE IES SENSITIVITY

SwingSmart uses a primary Type-A inherent
entrapment sensor (IES) per UL325 Safety
Standards. A solid immovable object blocking
the gate will trip the IES and cause the operator
to stop and reverse (for two seconds) and enter
safe mode.
The adaptive IES software monitors the average
running motor current while the gate is in motion
and reverses the gate when the current exceeds
an automatically self-adapting threshold.
The IES display, accessed through the Installer
Menu, allows you to input a number between 0 and
9. The settings (0 through 6) allow an increasingly
higher threshold (amount of headroom) above
the average current draw before tripping. For IES
settings 7 through 9, the current limit is a fixed
relatively high current value before the IES will be
tripped. The factory setting is 2, which is adequate
for most sites. See Figure 44 and Figure 45
CAUTION
Avoid setting the IES sensitivity to a fixed level
(7 - 9 setting). The high motor current required
for the IES to trip could cause severe injury or
death to people caught in the moving gate.
For IES settings (0 through 6), the motor current is
continually being measured and the IES threshold
automatically set to trip at peak motor current plus
the additional "headroom" provided by the IES
setting selected.
To prevent false IES trips, the software boosts the
IES current threshold for one gate cycle after an
IES event, then returns to the normal sensitivity
threshold.
Over time, degrading gate hardware and other
site issues, such as road settling or debris on the
gate rail (V-track) can occur. As the gate hardware
ages and becomes stiffer, the SwingSmart motor
current increases and this may create the need to
use a higher IES setting level. The higher settings
should only be used on a TEMPORARY basis until
the gate, gate track, or hinges are repaired so the
gates swingsmoothly with minimum resistance.
80
| www.hysecurity.com
DISPLAY AND MENU OPTIONS
SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL
SE 2
IES SENSITIVITY
OPEN
CLOSE
STOP
SELECT
PREV
NEXT
Figure 44. IES Sensitivity
Typical Opera�on
Installer Menu: IES Se�ng = 2
0
1 2
3 4 5 6
Time (Seconds)
Windy Day Opera�on
Installer Menu: IES Se�ng = 2
0
1 2
3 4 5 6
7 8 9 10 11 12
Time (Seconds)
Figure 45. IES Sensitivity Chart
NOTICE
When changing the IES setting, consider the
site design and vehicular gate traffic. It is
recommended that you use the most sensitive
setting while still allowing for reliable gate
operation.
MENU
RESET
Ini�al IES threshold
(First gate cycle only)
Motor current threshold
(at IES Se�ng 2)
Motor current
(under typical opera�ng
condi�ons)
7 8 9 10 11 12
Motor current threshold
Motor current spike (so�ware
compensates for wind load)
MX3640-01 REV. D ©2018