Connecting Hy-5B Vehicle Detectors - HySecurity SwingSmart DC Series Programming And Operations Manual

Pad-mounted electromechanical swing gate operator with smart dc controller
Table of Contents

Advertisement

There are four vehicle detector inputs available
on the Smart DC Controller:
z Free Exit Loop Detector - This opens a fully
closed gate or reopens a closing gate.
z Outside Obstruction Loop Detector (Out Obs
Loop) - Reversing loop on public side
z Inside Obstruction Loop Detector (In Obs Loop)
- Reversing loop on secure side
z Center Loop Detector - Not used for slide gates.
NOTICE
Standard box type 11 pin (24 Volt DC or 24 Volt
AC) vehicle detectors may be connected in the
traditional manner as described in "Installing
Standard 11-Pin Box Type Vehicle Detectors"
on page 93.

CONNECTING HY-5B VEHICLE DETECTORS

Install the HY-5B Vehicle Detector modules
according to the following procedure:
1. Turn off both AC and DC power switches.
2. Insert the locking end of the two white plastic
standoffs into the mounting holes on the
detector.
3. Plug the detector into the appropriate
socket along the right edge of the Smart DC
Controller board. Be careful to align the six
detector pins into the socket correctly (the
screws for tightening the terminals should face
toward the board), and then snap the standoffs
into the holes in the control box.
4. Route the loop wires through the holes
provided in the control box and connect the
loop leads to the two terminals on the HY-5B
detector. Tighten the terminal screws securely.
91
| www.hysecurity.com
5. Repeat Steps 1 through 3 for each HY-5B
6. To enable the detectors, turn on power. The
7. If the detector module is unplugged after it
Pressing the RESET button:
z Clears any errors
z Tunes the detectors on connected loops
z Un-installs any detectors that have been
8. The Smart DC Controller automatically governs
9. Sensitivity adjustment is available for each HY-
SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL
VEHICLE DETECTOR
detector.
detectors will immediately tune if they are
connected to loops. Make sure no cars or other
metal objects are over the loops.
is enabled, a communications alert (ALERT
10) will be triggered; if the fault continues an
error message, ERROR 3 "Detector Failed" is
displayed.
NOTICE
If there is any detector fault, the gate operator
functions as if the detector is triggered.
removed
frequency selection for all HY-5B detector
modules. This simplifies installation and
guarantees that there is no cross-talk between
multiple loops. The frequency can also be
manually selected; if this is required, refer to
"Table 12. Smart DC Controller - Installer Menu
Functions" on page 68.
5B in the installer menu. Generally, sensitivity
does not need to be increased unless the loop
is large or there are multiple loops connected
to one detector. The HY-5B sensitivity defaults
to automatic.
NOTICE
Do not exceed more than 200 square feet (61
square meters) of loop area to one detector.
MX3640-01 REV. D ©2018