HySecurity SlideDriver 15 Programming And Operations Manual

HySecurity SlideDriver 15 Programming And Operations Manual

With smart touch controller
Table of Contents

Advertisement

SlideDriver 15, 30F, 40, 80, 200
and SlideDriver 50VF 2/3
Programming & Operations Manual
with
HySecurity Smart Touch Controller
MX3630-01 Revision B
This document provides Important Safety Information, specifications, and references along with
an overview of programming user and installer menu options, designing vehicle loop layouts,
troubleshooting, and maintaining the gate operator.

Advertisement

Table of Contents
loading

Summary of Contents for HySecurity SlideDriver 15

  • Page 1 SlideDriver 15, 30F, 40, 80, 200 and SlideDriver 50VF 2/3 Programming & Operations Manual with HySecurity Smart Touch Controller MX3630-01 Revision B This document provides Important Safety Information, specifications, and references along with an overview of programming user and installer menu options, designing vehicle loop layouts,...
  • Page 2 Table 2: HySecurity Gate Operators maintaining Object Detection Table 2 indicates those HySecurity gate operators that may be within the exception parameters of UL 325 or comply with standards other than UL 325, but continue to maintain object detection capabilities. HySecurity strongly recommends that you assess every site for entrapment zones and provide the necessary protection to guard against entrapment.
  • Page 3 UL 325 compliant installation site. NOTE: Table 3 provides the list of sensors that are approved for use with HySecurity gate operators using the monitoring capabilities found in software versions h4.53 or h5.54 (or higher). These sensors are ETL listed or UL recognized to UL 325 and have been tested and approved by Intertek for use in HySecurity gate operators.
  • Page 4 SlideDriver 15, 30F, 40, 80, 200 SlideDriver 50VF Site Installation Overview Gate Face* Use shims as needed Grooved Drive Rail Screen Safety Mesh on Gate Height: Per UL 325 and ASTM F2200, all openings in a sliding gate up to a 72-inch (6 foot or 183 cm) height must be guarded or screened.
  • Page 5 Cover not shown Drive Arm, Motor Mount, Top Drive Arm, Motor Mount, Bottom Limit Hose Switches Release, Manual Motor, Hydraulic Combination AdvanceDrive and XtremeDrive Wheels (80 and 150 Models, only. Not available on 50VF series) www.hysecurity.com © 2017 Introduction MX3630-01 Rev. B...
  • Page 6 Vent plug Valve Coil, Quick Stop Valve, Quick Stop Valve, Braking Breather cap Valve, Check, Endhead Braking Kit Gauge, Pressure AWOG Valve, 2 Position Directional Valve Coil, Directional Quick Disconnect, Socket Reservoir MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 7: Table Of Contents

    HySecurity Gate Operators: UL 325 – 2016 ........................ii Table 1: HySecurity Gate Operators requiring External Monitored Entrapment Protection Sensors ......ii Table 2: HySecurity Gate Operators maintaining Object Detection ................ii Table 3: External Entrapment Protection Sensors Approved for Use with HySecurity Gate Operators ...... iii ...................1 elcome to ecurity Contact Information .................................2...
  • Page 8 Check Time and Date ..............................45 User Menu ..................................45 User Menu: Table 6 ................................46 Installer Menu ................................48 Installer Menu: Table 7 ..............................48 Setting the Close Timer ..............................54 Test the Operator ................................55 viii MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 9 Retro-Reflective Photo Eye Systems ........................84 Using Photo Eye Sensors instead of Vehicle Loops ......................85 Photo Eye Alignment Feature ............................86 .................87 nStalling enSorS Compatibility ................................88 Installation ...................................88 Gate Edge Function ..............................88 www.hysecurity.com © 2017 Table of Contents MX3630-01 Rev. B...
  • Page 10 Smart Touch: Wireless Edge, Wireless Gate Link ......................116 Smart Touch: Wired Edge with GEM-104 & Photo Eye ....................117 Smart Touch: WireLess Edge Gate Link & Photo Eye ....................118 SlideDriver Installer Checklist ............................119 Specifications ................................120 MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 11: Welcome To Hysecurity

    Our commitment to quality and innovation will become evident as the features and performance of the expertly engineered and manufactured SlideDriver become familiar to you. Thank you again for the confidence you’ve shown in becoming part of the HySecurity family and in choosing a premium, industry-leading product. HySecurity Gate, Inc. Headquarters in Kent, WA www.hysecurity.com...
  • Page 12: Contact Information

    Ontact nfOrmatiOn Qualified HySecurity distributors are experienced and trained to assist in resolving any problems. For the name of a qualified distributor near you, call HySecurity at 800-321-9947. Before contacting your distributor or HySecurity Technical Support, obtain the serial number of your operator.
  • Page 13: Important Safety Information

    Important Safety Information found in the HySecurity product manuals and review all the literature that accompanies the product. It is important that only qualified installers handle the installation of the HySecurity equipment and gate operator. A “qualified” installer has one of the following: •...
  • Page 14: Safety - Additional Installer Responsibility

    • Make sure all exposed pinch points are eliminated or any exposed pinch points, rollers and wheels are guarded. • External entrapment protection sensors must be used wherever the risk of entrapment exists. SAVE THESE INSTRUCTIONS MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 15: Identifying Gate Operator Category And Usage Class

    Class IV: Intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations, NOT servicing the general public, in which unauthorized access is prevented via supervision by security personnel. SAVE THESE INSTRUCTIONS www.hysecurity.com © 2017 Important Safety Information MX3630-01 Rev. B...
  • Page 16: Safety - Additional Installer's Responsibility, Continued

    NOTE: Gate operator instructions must be given to the owner per UL 325 Standard of Safety. • Take photographs of the completed installation site and save it in your business files. SAVE THESE INSTRUCTIONS MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 17: Safety - Owner/User Responsibility

    Be aware of the international, federal, and local codes in your area and how best to handle hazardous waste materials. The pump pack fluid, found in all hydraulic HySecurity operators, can be recycled. Gear oil, found in HySecurity electromechanical gate operators, can also be recycled. If the fluids are mixed or contaminated with any solvents or other chemicals, they become hazardous waste.
  • Page 18: Emergency Stop Button

    NOTE: For more information, refer to Drive Wheel Spring Tension (Adjustment of Manual Release) on page 101. Other types of release mechanisms exist. For example, the Fire and Emergency Access Lock Box is available through HySecurity distributors. Contact your distributor for more information. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series ©...
  • Page 19: Safety Notices

    Obey all safety messages that follow these symbols to avoid possible injury or death. Electrical Phase Ground - Danger - Entrapment Possible Attention Symbol Zone Pinch Point Symbol Keep Away - Take Note - www.hysecurity.com © 2017 Important Safety Information MX3630-01 Rev. B...
  • Page 20 Page intentionally left blank MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 21: Power

    Code (NEC) - Article 250 requires a separate earth ground in addition to the required equipment ground. HySecurity recommends grounding the operator with a separate earth ground rod (or a similar device in the case of crash products) to shield the operator against electromagnetism and other electrical signals that may cause, erratic operation with, or damage to, the Smart Touch Controller and other electrical parts.
  • Page 22: Site Considerations

    Site Considerations HySecurity gate operators are intended for permanent installation. Make sure you prepare the site with the following considerations: • Make sure all electrical wiring is properly routed via conduits. • Check the distance of the wiring run from the main panel to the gate operator. Make sure the wire size of the branch circuit supplying power to the gate operator is large enough to avoid excess voltage drop.
  • Page 23: Turning The Power Switch On

    STATUS SENSOR 3 Turning the Power Switch ON DO NOT USE CHARGER AC LOSS HySecurity The AC power disconnect switch is located on the same enclosure LOCK INTERLOCK MX000585 VERSION (control box) where the electrical components, Smart Touch EMERG CLOSE Controller, transformer, power supply board, etc., are found.
  • Page 24: Wire Sizing And Runs

    7.0 miles (11 km) 20 ga 3.5 miles (5.6 km) 22 ga 2.7 miles (4.3 km) 24 ga 2.0 miles (3.2 km) 26 ga 1.0 mile (1.6 km) 28 ga 3700 feet (1.1 km) MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 25: Slidedriver Wiring Charts (Incoming Power)

    1120 (341m) 975 (297m) 515 (157m) 475 (145m) 260 (79m) 2220 (670m) 1915 (584m) 1550 (472m) 815 (248m) 750 (229m) 410 (125m) 3550 (1082m) 3080 (939m) 2465 (751m) 1305 (398m) 1200 (366m) 650 (198m) www.hysecurity.com © 2017 Power MX3630-01 Rev. B...
  • Page 26 4650 (1417m) 2840 (866m) 2750 (838m) 1150 (350m) 11700 (3566m) 9350 (2850m) 7400 (2255m) 4550 (1387m) 4400 (1341m) 1800 (549m) 18500 (5639m) 14800 (4511m) 11700 (3566m) 7200 (2194m) 7000 (2134m) 2900 (884m) MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 27: Slidedriver 50Vf-Series Wiring Chart (Incoming Power)

    2530 (771m) 6990 (2130m) 8470 (2582m) Performance of 50VF-series Operators on 1 and 3 Phase, 50 or 60Hz A HySecurity 50VF-series operators can operate on a wide variety of incoming power. • 50Hz/60Hz operation with no changes or reconnection •...
  • Page 28 SlideDriver 50VF-series operators are NOT field reconfigurable between 208/230VAC and 460VAC power. The VFD Motor Controller in a 208/230VAC unit must be replaced with a VFD Motor Controller manufactured for the higher (460VAC) voltage input. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 29: Control Transformer Connections (Non-Ups)

    You need a 2-inch (5 cm) diameter conduit for hydraulic hoses and a ¾-inch (19 mm) conduit for electrical wiring. AC input power is connected to the hydraulic pump and electrical components enclosure (HydraSupply). A supplemental manual, provided with the product, describes the installation overview, wiring and conduit considerations. www.hysecurity.com © 2017 Power MX3630-01 Rev. B...
  • Page 30: Dc Power Supply (Ups) Connections

    When the local AC power fails, the UPS back up system continues to move the gate. System features are covered in the HyInverterAC Installation and Reference Manual shipped with the product and available online at www.hysecurity.com. NOTICE: The AC Power Supply with HyInverter AC option is intended for single phase (1 hp) gate operators and single phase (2 hp) gate operators that use Variable Speed Drives (VFD).
  • Page 31: Initial Setup

    All SlideDrivers are set at the factory for right handing. If the gate has left handing, the hydraulic hoses must be swapped. See page 22. OPEN OPEN Left-Hand Right-Hand Gate Gate www.hysecurity.com © 2017 Initial Setup MX3630-01 Rev. B...
  • Page 32: Hydraulic Hose Swap

    ¼-inch incremental turns on the adjustment stem with a hex key. Note that the adjustment screw varies depending on model type. 2. When the adjustment is complete, retighten the locking nut to hold the setting. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 33: Grounding, Breather Cap Installation & Handing

    “right hand” operation. Refer to Gate Handing on page 21. Factory set for right-handing. Swap hose connections for left- handing gate. Grade level Cut-away view Consult local codes for proper depth Concrete foundation Ground rod www.hysecurity.com © 2017 Initial Setup MX3630-01 Rev. B...
  • Page 34: Slidedriver Slow Down Limit Ramps

    Limit Ramp Kits. CAUTION Be sure to securely fasten all limit ramps to the underside of SlideDriver 50VF the drive rail when installing a 50VF-series operator. Slow Down Limit Ramp Kit MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 35: Adjusting The Pressure Relief Valve

    5 hp 2000 psi CAUTION Never exceed the maximum psi setting. Hex head adjustment screw Hex socket adjustment screw SlideDriver 15, 40, 50VF The Pressure Relief SlideDriver 30F, 80, 200 Valve is located behind the motor on the pump rack or soft start manifold.
  • Page 36: Modbus Rtu In Slidedriver 50Vf-Series

    Controller to constantly monitor the Variable Frequency Drive (VFD) and record events in the STC history log. The history log is easily accessible using the HySecurity S.T.A.R.T. program and a PC laptop computer or view history log codes by accessing the User Menu, LG item (software version h5.53 or higher).
  • Page 37: Emergency Fast Operate (Efo) In Slidedriver 50Vf-Series

    7. Press Select to accept the entry. (The display characters stop blinking.) 8. Press Menu to exit programming mode and return to Run mode. A Run mode gate status appears (example, GATE OPEN). www.hysecurity.com © 2017 Initial Setup MX3630-01 Rev. B...
  • Page 38: Installing A Push Button Device For Emergency Fast Operate (Efo)

    Smart Touch Controller SlideDriver 50VF2 2.2 fps (26 in per sec) 3 fps (91 cm/s) LIMIT DUAL GATE RADIO OPTIONS OPEN +24V +24V SlideDriver 50VF3 3 fps (91 cm/s) 3 fps (91 cm/s) MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 39: Entrapment Protection

    UL 325 - 2016 manufacturing dates. Build Year (BY) is a factory-setting. Build Year 2 (BY 2) is the default for all HySecurity gate operators indicating a manufacturing date of 2016 in the serial number. Replacement controller boards for existing sites allow for a Build Year setting of 1 (BY 1, pre-2016).
  • Page 40: Inherent Entrapment Sensor System - Hydraulic Operators (Ies)

    The IES on HySecurity gate operators is an entrapment sensor that is required by UL 325 as a Type “A” detection sensor. It is tripped through software programming OR hydraulic pressure settings. It does not function solely on its own accord and must be connected to the Smart Touch Controller. The sensitivity and response of the IES when tripped is factory set, but can be adjusted through the Installer Menu items: •...
  • Page 41: How Software Handles Monitoring External Entrapment Protection Sensors

    NOTE: All HySecurity gate operators, indicating a manufacturing date of 2016 in the serial number, will have the Build Year set to 2. A Build Year of 2 (BY 2) indicates that your gate operator is prepared to monitor for external entrapment protection sensors.
  • Page 42 NOTE: When installing wired edge sensors, the wired edge must be connected to an interface module with an NC output. See Wiring HySecurity Sensors: Smart Touch on page 109. For wireless edge sensors, no interface module is required. Wireless edge sensors need the wireless gate links which include a transmitter and receiver.
  • Page 43 ● HydraLift NOTE: HySecurity does not update software for SlideWinder models. For information regarding HySecurity gate operators not shown in the table above, refer to Table 2: HySecurity Gate Operators maintaining Object Detection on page ii. www.hysecurity.com © 2017 Entrapment Protection...
  • Page 44: Supply Power To The Sensors

    All external entrapment protection sensors must be wired to the SENSOR COM terminal for monitoring purposes. Review sensor wiring diagrams found in Wiring HySecurity Sensors: Smart Touch on page 109. Until the gate operator receives a command to run (open or close command), the sensors are not receiving power.
  • Page 45: C Ontrol P Anel O Verview

    Provides inputs for peripherals and accessories, 2 electromechnical user relays (250VAC, 10A), one solid Power Switch state user relay (30VDC, 3A). For more information, refer to STC Terminal Inputs on page www.hysecurity.com © 2017 Control Panel Overview MX3630-01 Rev. B...
  • Page 46: Slidedriver Wiring Diagram, D0266 Rev B

    DO NOT USE CHARGER AC LOSS HySecurity LOCK INTERLOCK MX000585 VERSION EMERG CLOSE FIRE DEPT OPEN Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS OPEN +24V +24V DUAL GATE HYSECURITY GATE STOPPED MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 47: Variable Speed Drive (Vfd) Control Box

    (Non-UPS) on page 19. label found on the operator’s name control handling. plate. CAUTION Residual voltage remains in the VFD which can cause electrical shock to personnel or damage to the equipment. www.hysecurity.com © 2017 Control Panel Overview MX3630-01 Rev. B...
  • Page 48: Variable Speed Drive Wiring Diagram

    123456 LEGEND 1 COMMON 2 MENU 3 RESET 4 OPEN 5 CLOSE END OF TRAVEL 6 STOP LIMITS DIRECTIONAL VALVE IES SENSOR SLOW DOWN LIMITS NOTE: DRAWING IS NOT TO SCALE. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 49: Stc Board, Power Supply Board And Display

    CLOSE DIRECTION VERSION EMERG CLOSE Updated silk screen label FIRE DEPT OPEN incorporated Smart Touch Controller January 2016. LIMIT DUAL GATE RADIO OPTIONS OPEN +24V +24V Smart Touch Controller Ribbon cable www.hysecurity.com © 2017 Control Panel Overview MX3630-01 Rev. B...
  • Page 50 Page intentionally left blank MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 51: D Isplay & M Enu O Ptions

    NOTE: Use a laptop computer at your place of business to conveniently download the free START software and most current software version from www.hysecurity.com before heading out into the field. This makes it easy to adjust settings using a laptop.
  • Page 52: Menu Mode And The Stc Keypad

    Press Select. Press Next or Previous. Press Select. Continue pressing Next to view Blinking characters Advance - press Next Two left characters blink. all selections. become static. Previous - press Previous MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 53: Run Mode And The Stc Keypad

    Pressing Reset clears alerts or faults and returns to Run Mode. 32-character display NOTE: Press Reset at identifies operator any Run mode status status. HYSECURITY HYSECURITY HYSECURITY GATE OPEN GATE CLOSED GATE STOPPED display to view the software version. For example: h4.53...
  • Page 54: Stop The Status Display Scrolling

    The software version can also appear when you cycle power. Before contacting Technical Support, know the software version on your gate operator and have the gate operator serial number available. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 55: Check Time And Date

    Refer to the chart, Smart Touch Controller: Menu Mode Navigation Buttons on page 42. Table 6 describes the User Menu items and supplies the factory defaults. (Factory default settings shown in bold.) www.hysecurity.com © 2017 Display & Menu Options MX3630-01 Rev. B...
  • Page 56: User Menu: Table 6

    Set to 3: Available on barrier operators only and UC 4 if sensor inputs set to 1 “NOT USED”. Buzzer beeps when gate starts to move and continues throughout gate travel. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 57 PC laptop loaded 1 to record all operator open and close events, in with HySecurity free addition to the normal alert, fault and error logs. This S.T.A.R.T. software is parameter automatically resets to the default 0 (off) required.
  • Page 58: Installer Menu

    NOTE: Installer Menu options can also be configured through the use of a laptop computer and S.T.A.R.T. software. See Smart Touch Analyze and Retrieve Tool information found on the HySecurity website: www.hysecurity.com Table 7 describes the Installer Menu items and supplies the factory defaults. (Factory settings shown in bold.)
  • Page 59 (Security Gate) NOTE: After selecting SG settings, consider A to A accessing the User Menu in each gate B to B operator to address the Close Timer (CT) setting. www.hysecurity.com © 2017 Display & Menu Options MX3630-01 Rev. B...
  • Page 60 7 to 99 seconds PARTIAL OPEN an adjustable distance by setting the open duration. The available time settings are 7 to 99 seconds. The default setting [PO 0] leaves this input inactive. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 61 Same as Sensor 1 SENSOR 2 SENSOR #2 TYPE +24V SENSOR COM S3 0 Same as Sensor 1 Same as Sensor 1 SENSOR 3 SENSOR #3 TYPE +24V SENSOR COM www.hysecurity.com © 2017 Display & Menu Options MX3630-01 Rev. B...
  • Page 62 NOTE: The shaded Installer Menu items do not appear when Build Year is set to 2 (BY 2). Exceptions exist for barrier arms, CRASH products, operators set to pre-2016 and Usage Class IV provisions. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 63 RS-485. Involves STC ADDRESS 1 to 99 = Network “drop” address communication. 1 – 99 sets individual poling additional addresses. hardware & Refer to HyNet™ literature for more software. information. www.hysecurity.com © 2017 Display & Menu Options MX3630-01 Rev. B...
  • Page 64: Setting The Close Timer

    1. At a gate status display, press the Menu button twice. This accesses the User Menu and the Close Timer display appears. NOTE: If you want gate personnel to operate the gate with the Hold to Close feature found in some push MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 65: Test The Operator

    It will close a second or two faster than normal operation and ignore any photo eye, vehicle loop, or other safety sensor inputs. NOTE: If additional accessories are to be added, read about STC Inputs & Wiring on page 57. XtremeDrive (rack) shown www.hysecurity.com © 2017 Display & Menu Options MX3630-01 Rev. B...
  • Page 66 Page intentionally left blank MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 67: Stc Inputs & Wiring

    Fire Department Open** - 24 RS-232 Connector Smart Touch Controller Tact Push Button Switch LIMIT DUAL GATE RADIO OPTIONS Weigand Connector OPEN +24V +24V Limit Switch Master Open Gate Connectors Slave Radio Edge Radio www.hysecurity.com © 2017 STC Inputs & Wiring MX3630-01 Rev. B...
  • Page 68: Overview Of The Stc And Power Supply Board

    3 terminals. Any combination of the 5 available terminals can be used to draw Smart Touch Controller RADIO OPTIONS LIMIT DUAL GATE the 3A maximum. OPEN +24V +24V Tact button Smart Touch Controller LOOP Not to Scale MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 69: Integrating With Security Systems And Hynet™ Gateway

    The RS-485 interface is also used to communicate with the HyNet Gateway, a web-enabled interface. To view the user guide and quick start information regarding HyNet Gateway SFP 4/1, go to the HySecurity website, Technical_Support_Installation_Manuals.
  • Page 70: Smart Touch Controller Inputs

    Singular button device Button Button radio controls. (multi-function) NOTE: Terminal is only used in Open Partial Open Partial Monitored access slide gates. Adjustable through controls the Installer Menu from 7 to 99. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 71 VEHICLE DETECTOR Common on page 31 and Wiring run command. SHADOW/RESET VEHICLE DETECTOR HySecurity Sensors: Smart Use these terminals to SENSOR 1 Touch on page 109. preserve battery power. SENSOR NOTE: For pre-2016 gate operators, inputs...
  • Page 72 Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS OPEN +24V +24V NOTE: See Wiring HySecurity Sensors: Smart Touch on page 109, for photo eye and gate edge connections. LOOP Not to Scale MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 73: User Relays - Programming Procedure

    7/10ths of a second before the operator starts moving the gate and remains active while moving. Output remains active, for a few seconds, after stopping. www.hysecurity.com © 2017 STC Inputs & Wiring MX3630-01 Rev. B...
  • Page 74 * Preferred connection is Relay 3, a solid state relay (except on Crash). On Crash gate operators, Relay 3 is unavailable because it is hard-wired for the LED barrier arm lights. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 75 Relay 1, 2 or 3 relay is constantly activating except when the open limit switch is triggered or AC power fails. Set aside for Factory Use HySecurity Testing Only Do not use Arm Break Does not appear. Used on StrongArm and StrongArmPark DC and activates if the breakaway arm switch is tripped.
  • Page 76: Hy8Relay Module Option

    Table 8. Wire communication cable connections between the DUAL GATE ports, at the base of the STC, and the extended mechanical relay module. Refer to instructions that accompany the Hy8Relay Module. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 77: Bi-Parting & Dual Gate Systems

    NOTE: Both SlideDriver gate systems need to have compatible software versions installed on their Smart Touch Controllers. Bi-parting SlideDrivers www.hysecurity.com © 2017 Bi-Parting & Dual Gate Systems MX3630-01 Rev. B...
  • Page 78: Dual Gate Wiring Connections

    DO NOT USE STATUS STATUS SENSOR 3 SENSOR 3 DO NOT USE DO NOT USE CHARGER CHARGER AC LOSS AC LOSS HySecurity HySecurity LOCK INTERLOCK LOCK INTERLOCK MX000585 MX000585 VERSION VERSION EMERG CLOSE EMERG CLOSE FIRE DEPT OPEN FIRE DEPT OPEN...
  • Page 79: Dual Or Sequenced Gates: Power, Software & Accessory Requirements

    RESET button. • For up-to-date features, keep the most current software loaded on both gate operators. Software downloads are available at www.hysecurity.com. Make it part of your maintenance routine to check for and install software updates on a regular basis. •...
  • Page 80: Connecting Sequenced Gates

    DO NOT USE STATUS STATUS SENSOR 3 SENSOR 3 DO NOT USE DO NOT USE CHARGER CHARGER AC LOSS AC LOSS HySecurity HySecurity LOCK INTERLOCK LOCK INTERLOCK MX000585 MX000585 VERSION VERSION EMERG CLOSE EMERG CLOSE FIRE DEPT OPEN FIRE DEPT OPEN...
  • Page 81 SG 4 = Sequenced Gate #4 configuration (only used with HydraSupply XL) NOTE : Set gate operators on the site to the uniquely paired number. Refer to the site designs on the following pages. www.hysecurity.com © 2017 Bi-Parting & Dual Gate Systems MX3630-01 Rev. B...
  • Page 82: Sequenced Gate: Configuration #1

    If a communication failure occurs, an ALERT 22 (AL  22) appears and the buzzer sounds. The Traffic Control Gate maintains functionality while the Security Gate defaults to Drawings not to scale. open until communication is restored (or the Security Gate is manually closed). MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 83: Sequenced Gate: Configuration #2

    If a communication failure occurs, an ALERT 22 (AL  22) appears and the buzzer sounds. The Traffic Control Gate maintains functionality while the Security Gate defaults to Drawings not to scale. open until communication is restored (or the Security Gate is manually closed). www.hysecurity.com © 2017 Bi-Parting & Dual Gate Systems MX3630-01 Rev. B...
  • Page 84 Page intentionally left blank MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 85: I Nstallation And

    Vehicle Detector Installation and Logic HySecurity recommends that vehicle detectors be used for free exit and obstruction sensing logic only. The exception is in parking or barrier arm applications where detectors may also be used to close the gate. In applications employing our swing, vertical lift, or sliding gate operators, closing logic cannot be used except when the anti-tailgate logic is employed.
  • Page 86: Vehicle Detector Installation: Hy-5A

    The Smart Touch Controller provides an interface for up to four different vehicle detector functions. NOTE: Standard box type 11 pin (24 VDC or 24 VAC) vehicle detectors may be connected in the traditional manner, but HySecurity HY-5A mini-detector modules plug directly into the Smart Touch Controller, making field installation much faster and enhancing performance.
  • Page 87: Connecting Hy-5A Vehicle Detectors

    NOTE: For illustrations and detailed instructions, refer to the literature supplied with the HY-5A vehicle detectors. The installation instructions are also available online at www.hysecurity.com Install each HY-5A vehicle detector module, one at a time using the following steps: 1. Turn off the AC power switch on the Control Box.
  • Page 88: View Call Level In Real Time

    If the test outcome is good and all the loops are operating properly, you may need to adjust the HY-5A sensitivity dial, so the call level reads in the 5 to 6 range. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 89: Installing Standard 11-Pin Box Type Vehicle Detectors

    Loop Detector DO NOT USE SENSOR 2 DO NOT USE STATUS SENSOR 3 DO NOT USE CHARGER AC LOSS HySecurity LOCK INTERLOCK VEHICLE LOOP MX000585 VERSION EMERG CLOSE FIRE DEPT OPEN Common Smart Touch Controller To LOOP terminal on Smart Touch Controller...
  • Page 90 Page intentionally left blank MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 91: Photo Eye Installation

    NOTE: To enable fully automatic operation, this gate operator requires a MINIMUM of one external entrapment protection sensor to monitor potential entrapment zones in either the open or close direction of travel. Visit www.hysecurity.com/gatesafety for more information on UL 325 standards and gate safety.
  • Page 92: Photo Eyes (Non-Contact) Installation

    Compatibility The UL 325 standard requires that a photoelectric sensor be laboratory tested and “recognized” under UL 325. In order to be compatible with all HySecurity operators, a photo eye must be rated to function from 24 VDC source power.
  • Page 93: Configuration

    HySecurity Sensors: Smart Touch on page 109. NOTE: HySecurity gate operators, manufactured with 2016 (or later) in the serial number, require Normally Closed output sensors. Some manufacturers label an output as N.O. (normally open), when it is actually an N.C. (normally closed) contact. Review Table 3:...
  • Page 94: Retro-Reflective Photo Eye Systems

    Realign the eye for the position of the reflector. NOTE: If the photo eye is realigned, be sure to perform the centering test again to verify that the reflector is truly in the center. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 95: Using Photo Eye Sensors Instead Of Vehicle Loops

    UL 325 Standard of Safety for “monitored” external entrapment protection. To understand external SENSOR 1 entrapment protection and how HySecurity equipment Photo Eye sensor terminal connections when monitors sensors, refer to the section titled Entrapment PE sensors used in place of vehicle loops Protection on page 29.
  • Page 96: Photo Eye Alignment Feature

    Press Select. Press Next or Previous. Press Select. Continue pressing Next to view Blinking characters Advance - press Next Two left characters blink. all selections. become static. Previous - press Previous MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 97: Installing Gate Edge Sensors

    Refer to Table 3: External Entrapment Protection Sensors Approved for Use with HySecurity Gate Operators on page iii. To enable fully automatic operation, this gate operator requires a MINIMUM of one external entrapment protection sensor to monitor potential entrapment zones in either the open or close direction of travel.
  • Page 98: Compatibility

    The UL 325 standard requires that a gate edge sensor be laboratory tested and “recognized” under UL 325. In order to be compatible with all HySecurity operators, a gate edge sensor must be rated to function from 24 VDC source power. For a list of compatible sensors, see Table 3 on page iii.
  • Page 99: Troubleshooting

    Alert buzzer emits distinctive chirping sounds. Any Alert, Fault, or Error is logged into memory and stamped with the date and time. These diagnostic messages can be retrieved for analysis purposes via optional S.T.A.R.T. software and a PC laptop. NOTE: S.T.A.R.T. configuration and diagnostic software is available at no charge from www.hysecurity.com. www.hysecurity.com © 2017 Troubleshooting...
  • Page 100: Troubleshooting Codes: Table 9

    • Review wiring diagrams. Especially path to SENSOR COM • Make sure SENSOR settings S1, S2, and S3 are correctly assigned. Refer to External Entrapment Protection Sensors: What the Installer Needs to Do on page 31. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 101 ALERT 10 2 chirps per second every 15 Communication issue between the HY-5A and the Smart Touch I2C BUS ERROR seconds Controller; reset and try again. Replace the HY-5A if the problem continues. www.hysecurity.com © 2017 Troubleshooting MX3630-01 Rev. B...
  • Page 102 VFD is experiencing a fatal error. If you cannot clear the error alert by pressing the open or close button, contact HySecurity. ALERT ALERT 22 2 chirps per second every 3...
  • Page 103 Check the wiring. Refer to the wiring diagram associated with the attached sensor. See Wiring HySecurity Sensors: Smart Touch on page 109. Be sure the eye “common” wire is wired properly to the SENSOR COM terminal.
  • Page 104 Check wiring from the hydraulic cylinder to the STC. RPM SENSOR minute ERROR ERROR 9 3 chirps per second once per Only applies to DC Power Supply connection. Contact HySecurity. BATT DISCONNECT minute MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 105: Access The Event Log Through The User Menu

    Month / Day Time (HH:MM) Event Type 03/17 15:27 ALE5 Description: ALERT 5: BOTH LIMITS TRIPPED NOTE: Over 300 events can be recorded before the software begins overwriting the existing log history. www.hysecurity.com © 2017 Troubleshooting MX3630-01 Rev. B...
  • Page 106: Electrical Issues

    12. With the knowledge that the power is correct and the electric motor runs, check the STC display. If an error, alert or fault code appears, refer to Troubleshooting Codes: Table 9 on page 90 to determine possible resolutions. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 107: Mechanical Issues

    NOTE: If the gate speed must be changed, contact your HySecurity distributor or HySecurity Tech Support. Extremely cold weather is unlikely to seriously affect the gate speed because HySecurity employs a special grade of hydraulic fluid (Uniflow), which maintains a linear viscosity over a broad temperature range.
  • Page 108: Typical Problems And Troubleshooting Procedures

    Eye Alignment Feature on page 86 and Eye Close Logic (EC) in Troubleshooting on page 89. If you have a battery-powered photo eye, check that the batteries are viable and the batteries are fresh. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 109: General Maintenance

    With S.T.A.R.T. software loaded on your laptop computer, you have an invaluable management tool for all HySecurity operators. The RS-232 serial port (found on the Smart Touch Controller), allows you to download system diagnostics and upload system configurations using the S.T.A.R.T. software. The free S.T.A.R.T. software is conveniently located at www.hysecurity.com.
  • Page 110: Software Maintenance

    The software on the STC board is periodically being enhanced with new features that create an easier install and improve the on-board diagnostic tools. Be sure to check the HySecurity website for the latest version of software and operator code before heading out for field maintenance.
  • Page 111: Mechnical Controls

    OntrOLS Stopping the Gate Most models (except SlideDriver 15 and 40) employ a time delay Soft Stop system. Additionally, brake valves are used to control the stopping of heavy or fast moving gates. These valves are exclusive to HySecurity operators. They are independently adjustable to allow the gate to stop predictably and without banging.
  • Page 112: Drive Rail

    (24 to 25 cm) from base of SlideDriver chassis if using XtremeDrive™ wheels. Review SlideDriver Slow Down Limit Ramps on page 24. AdvanceDrive™ Wheel Drive Rail (standard) Rack XtremeDrive™ Wheel XtremeDrive™ System MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 113: Drive Wheel Spring Tension (Adjustment Of Manual Release)

    Controls drive wheel gripping force. Set at 2 in. (5 cm) when Drive Wheels are Coupling Nut: clamped on the Drive Rail. Toggle handle Adjusts compression spring. is in the clamped (load) position. www.hysecurity.com © 2017 General Maintenance MX3630-01 Rev. B...
  • Page 114: Grooved Drive Rail

    NOTE: The non-grooved, flanged drive rail is still available for use with the Solenoid Lock option. The Solenoid Lock option requires an outer edge flange and therefore must be installed with the non-grooved, flanged drive rail. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 115: Drive Wheel Assembly

    Drive wheel assembly tasks are slightly different depending on the type: AdvanceDrive™ or XtremeDrive™. NOTE: Installation instructions are provided with the replacement drive wheels and are accessible online at www.hysecurity.com. A quick look at the drive wheel assembly is shown below. Tighten drive wheel mounting bolts to 25 ft lb.
  • Page 116: Hydraulic System Maintenance

    3. Fill to within ½ inch of the plug level, and then replace plug. NOTICE: Never use brake fluid. It will severely damage the hydraulic system. Use of any fluid other than fluid recommended by HySecurity may void the operator warranty. Solenoid Look for leaks: Occasionally there may be slight seeping at the fittings after some usage.
  • Page 117: Brake Valve Adjustments

    The open valve is solenoid operated and, when energized, directs the hydraulic flow to open the gate. No adjustment of this valve is possible or necessary. The black solenoid coil mounts on its valve stem. www.hysecurity.com © 2017 General Maintenance...
  • Page 118: Slidedriver Operator Maintenance Schedule

    Special Notes: *1. Your gate and gate hardware will require more maintenance than your HySecurity operator. A damaged gate or worn hardware may cause slow or erratic operation and will result in excess drive wheel wear. Lubricate gate hardware more frequently and check for smooth operation by opening the toggle clamping mechanism and then pushing the gate manually.
  • Page 119: Wiring Hysecurity Sensors: Smart Touch

    Wiring diagrams are provided on the following pages. The diagrams illustrate how to connect sensors and program the gate operator. HySecurity Smart Touch gate operators can monitor entrapment protection sensors per UL 325 - 2015 Standard of Safety using software version h4.50 (or higher).
  • Page 120: Wiring Tips For Sensor Com Terminal: Smart Touch

    Press Select. Press Next or Previous. Press Select. Continue pressing Next to view Blinking characters Advance - press Next Two left characters blink. all selections. become static. Previous - press Previous MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 121: Smart Touch: Wired Edge Sensor With Gem (-104)

    *NOTE: Make sure whichever wired input used (SENSOR 1, 2, or 3) is the MX000585 VERSION same Sensor # configured through the Installer Menu. EMERG CLOSE FIRE DEPT OPEN Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS OPEN +24V +24V www.hysecurity.com © 2017 Wiring HySecurity Sensors: Smart Touch MX3630-01 Rev. B...
  • Page 122: Smart Touch: Photo Eye Thru Beam (Emx Irb Mon)

    DIP switches must be set as shown otherwise the photo eye will not operate correctly. If you receive an Alert, "!ACTION BLOCKED" "Photo Eye Open" PEO or "Photo Eye Close" PEC, take steps to align the photo eye. Refer to See Photo Eye Alignment Feature on page 86. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 123: Smart Touch: Photo Eye / Reflective (E3K R10K4)

    BLOCKED" "Photo Eye Open" PEO or "Photo Relay NO (Terminal 5, NO2) Eye Close" PEC, take steps to align the photo eye. Refer to See Photo Eye Alignment Feature on page 86. www.hysecurity.com © 2017 Wiring HySecurity Sensors: Smart Touch MX3630-01 Rev. B...
  • Page 124: Smart Touch: The Solution, Mim-62 (Multi-Input Module)

    All external entrapment protection sensors must be NC sensor outputs and wired to the SENSOR COM terminal for monitoring and powering purposes. The sensor becomes actively powered when the gate operator's motor runs. MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 125: Smart Touch: Photo Eye / Reflecti-Guard (Rg-R)

    NOTE: If you receive an Alert, "!ACTION BLOCKED" "Photo Eye Open" PEO or "Photo Eye Close" PEC, take steps to align the photo eye. Refer to See Photo Eye Alignment Feature on page 86. www.hysecurity.com © 2017 Wiring HySecurity Sensors: Smart Touch MX3630-01 Rev. B...
  • Page 126: Smart Touch: Wireless Edge, Wireless Gate Link

    Test button on the Transmitter Wireless Edge Link (Receiver) to complete the LEARN mode MGL - RX20 process and sync the receiver and Signal received from battery- transmitter. powered Transmitter (MGL - TX20) MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 127: Smart Touch: Wired Edge With Gem-104 & Photo Eye

    NC sensor outputs and wired to the SENSOR COM Green Wires* terminal for monitoring and powering purposes. The sensor becomes actively powered when the *Green output wire can attach to gate operator's motor runs. any SENSOR input. www.hysecurity.com © 2017 Wiring HySecurity Sensors: Smart Touch MX3630-01 Rev. B...
  • Page 128: Smart Touch: Wireless Edge Gate Link & Photo Eye

    Use receivers & transmitters Version 1.02 or higher. OUTPUT DIP switches for CH1 and CH2. Verify dip switch is set to “R” for each channel used. HySecurity uses NC SELECT "Relay" sensors. Do NOT select "P" as the output. P = "Pulse" device.
  • Page 129: Slidedriver Installer Checklist

    HeckLiSt This check list is provided by HySecurity and is to be used after installing a SlideDriver gate operator. 1. Before checking the items in this list, make sure power is turned OFF at the main power disconnect and the operator’s control box power switch is also in the OFF position.
  • Page 130 UL 325 standards. 8. Sensors programmed properly. Date: Operator Serial Number: ____________________________________________________________________ Installer Name (please print): _________________________________________________________________ End user’s name (please print): ________________________________________________________________ Site address: _______________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________ Notes: ____________________________________________________________________________________ ___________________________________________________________________________________________ MX3630-01 Rev. B SlideDriver/SlideDriver 50VF Series © 2017 www.hysecurity.com...
  • Page 131 3. Buyer’s Exclusive Remedies for Any Nonconformity. Operator: Two Years or 500,000 gate cycles (whichever occurs first) after the If a HySecurity product fails to conform to the warranties in Section 1, Buyer must date of installation; notify and order replacement parts from the Distributor through which the product...
  • Page 132: Specifications

    To enable fully automatic operation, this gate operator requires a MINIMUM of one external entrapment protection sensor to monitor potential entrapment zones in either the open or close direction of travel. Visit www.hysecurity.com/gatesafety for more information on UL 325 standards and gate safety Copyright Notice ©...