Configuring

3.1

EMC-compliant installation of a machine or system

The converter is designed for operation in industrial environments.
Reliable and disturbance-free operation is only guaranteed for EMC-compliant installation.
Further information
Additional information about EMC-compliant installation is available in the Internet:
EMC installation guideline (http://support.automation.siemens.com/WW/view/en/60612658)
3.1.1

Control cabinet

Control cabinet assembly
● Install a shield support for shielded cables that are routed out of the control cabinet.
● Connect the PE bar and the shield support to the control cabinet frame through a large
surface area to establish a good electrical connection.
● Mount the converter, the 24 V DC power supply and the optional line filter on a bare metal
mounting plate.
● Connect the mounting plate to the control cabinet frame and PE bar and shield support
through a large surface area to establish a good electrical connection.
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
3
35