Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bandwidth referred to the time slice clock cycle of the function generator has either been set too low or too high.
Depending on the time slice clock cycle, the bandwidth is defined as follows:
Bandwidth_max = 1 / (2 x time slice clock cycle)
Bandwidth_min = Bandwidth_max / 100000
Example:
Assumption: p4830 = 125 µs
--> Bandwidth_max = 1 / (2 x 125 µs) = 4000 Hz
--> Bandwidth_min = 4000 Hz / 100000 = 0.04 Hz
Note:
p4823: Function generator bandwidth
p4830: Function generator time slice clock cycle
Remedy:
Check the value for the bandwidth and adapt accordingly.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02047
Function generator: Time slice clock cycle invalid
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time slice clock cycle selected does not match any of the existing time slices.
Remedy:
Enter an existing time slice clock cycle. The existing time slices can be read out via p7901.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02050
Trace: Start not possible
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace has already been started.
Remedy:
Stop the trace and, if necessary, start again.
A02051
Trace: recording not possible as a result of know-how protection
Message value:
initiating recorder: %1, parameter %2
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE