Faults and alarms
13.2 List of faults and alarms
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged once the permissible temperature limit minus 5 K has been undershot.
Note:
HF Damping Module
F37040
HF Damping Module: 24 V undervoltage
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Failure of the 24 V power supply for the HF Damping Module.
- the undervoltage threshold was undershot for longer than 3 ms.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the 24 V DC voltage supply of the HF Damping Module.
- carry out a POWER ON (switch-off/switch-on) for the component.
Note:
HF Damping Module
A37041 (F)
HF Damping Module: 24 V undervoltage alarm
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Fault in the 24 V power supply for the HF Damping Module.
- the 16 V threshold was undershot..
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the 24 V DC voltage supply of the HF Damping Module.
- carry out a POWER ON (switch-off/switch-on) for the component.
Note:
HF Damping Module
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY (POWER ON)
F37043
HF Damping Module: 24 V overvoltage
Message value:
-
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
Overvoltage of the 24 V power supply for the HF Damping Module.
- the 31.5 V threshold was exceeded for more than 3 ms.
Remedy:
Check the 24 V DC voltage supply of the HF Damping Module.
Note:
HF Damping Module