Pn: Cyclic Connection Interrupted; Pn: Maximum Number Of Controllers Exceeded; Pn: Second Controller Missing; Pn: System Redundancy Switchover Running - Siemens SINAMICS S210 Operating Instructions Manual

Servo drive system
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Faults and alarms
13.2 List of faults and alarms
A01980

PN: cyclic connection interrupted

Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFINET controller is interrupted.
See also: r8936 (PN cyclic connection state)
Remedy:
Establish the PROFINET connection and activate the PROFINET controller in the cyclic mode.
A01981

PN: Maximum number of controllers exceeded

Message value:
Info. 1: %1, info. 2: %2
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A controller attempts to establish a connection to the drive, and as a consequence exceeds the permitted number of
PROFINET connections.
The alarm disappears automatically after approx. 30 seconds.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info 1 = 0: number of RT connections exceeded
Info 1 > 0: number of IRT connections exceeded
Info 2: permitted number of connections
Remedy:
Check the configuration of the PROFINET controllers.
A01982

PN: second controller missing

Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Connections to two PROFINET controllers are expected. However, only the connection to a PROFINET controller is
present.
- there is only one connection to the F controller.
- system redundancy is activated.
Remedy:
Check the configuration of the PROFINET controllers.
A01983

PN: system redundancy switchover running

Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "PROFINET system redundancy" function is configured and the connection between the primary control and drive
device is interrupted. The backup controller assumes control of the drive device.
Remedy:
Not necessary.
The alarm is automatically withdrawn after switchover has been successfully completed.
A01989
PN: internal cyclic data transfer error
Message value:
%1
Drive object:
All objects
Reaction:
NONE
404
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fk2

Table of Contents