Remedy:
- use a Motor Module/Hydraulic Module that supports the safety-related functions.
- upgrade the Motor Module/Hydraulic Module software.
Note:
CU: Control Unit
SI: Safety Integrated
F01663

SI P1 (CU): Copying the SI parameters rejected

Message value:
-
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Using the commissioning tool, copy the Safety Integrated parameters - or were entered offline.
This is the reason that when booting, an attempt is made to copy Safety Integrated parameters from monitoring channel
1 to monitoring channel 2. However, no safety-relevant function has been selected in monitoring channel 1 (p9501 = 0,
p9601 = 0). Copying was rejected for safety reasons.
As a consequence, inconsistent parameterization can occur in both monitoring channels, which in turn results in additional
error messages.
Especially for inconsistent enabling of the safety functions on both monitoring channels, fault F30625 is output.
Note:
This fault does not result in a safety stop response.
SI: Safety Integrated
Remedy:
- check p9501 and p9601 and if required, correct.
- perform copy function using the commissioning tool.
- save all parameters or "Copy RAM to ROM".
- carry out a POWER ON (switch-off/switch-on).
F01664

SI P1 (CU): No automatic firmware update

Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
During booting, the system detected that the "Firmware update automatic" function (p7826 = 1) was not activated.
This function must be activated for automatic firmware updates/downgrades to prevent impermissible version combinations
when safety functions are enabled.
Note:
This fault does not result in a safety stop response.
Remedy:
When safety functions are enabled (p9501 <> 0 and/or p9601 <> 0):
1. Activate the "Firmware update automatic" function (p7826 = 1).
2. Backup the parameters (p0977 = 1) and carry out a POWER ON.
When deactivating the safety functions (p9501 = 0, p9601 = 0), the fault can be acknowledged after exiting the safety
commissioning mode.
F01665

SI P1 (CU): System is defective

Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
Faults and alarms
13.2 List of faults and alarms